Form No. PDS580F-36-4COMMERCIALSINGLE PACKAGE ROOFTOP UNITSGAS HEATING/ELECTRIC COOLING UNITSStandard efficiency units (580F072, 090, 120, 150 and579F
10ARI* CAPACITY RATINGS — 580F036-151 LEGEND*Air Conditioning and Refrigeration Institute.†Applies only to units with capa
100PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in
101PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in
102PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in
103PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in
104PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGENDNOTES:1. Direct interp
105PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in
106PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in
107PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied d
108PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 770 to 1185 rpm. All other rpms require field-sup
109PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-su
11ARI* CAPACITY RATINGS (cont)HEATING CAPACITIES AND EFFICIENCIES (Standard Efficiency Units) — 580F036-151 (cont)208/230/460-3-60 — SINGLE-STAGE GAS
110PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-su
111PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-su
112PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All othe
113PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All othe
114PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All othe
115PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All othe
116PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All othe
117PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All othe
118PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All othe
119PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field- sup
12ARI* CAPACITY RATINGS — 581B036-150 LEGEND*Air-Conditioning & Refrigeration Institute.†Applies only to units with capaci
120PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 770 to 1185 rpm. All other rpms require field-s
121PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-
122PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
123PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1686 rpm. All other rpms require field-
124PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All ot
125PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All ot
126PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All ot
127PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All ot
128PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All ot
129PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All ot
13ARI* CAPACITY RATINGS (cont)HEATING CAPACITIES AND EFFICIENCIES — 581B036-150(cont)208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx208/230/460-3-6
130PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All ot
131PERFORMANCE DATA (cont)FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581B036-150*Approximate fan rpm shown (standard motor/drive).FAN RPM
132PERFORMANCE DATA (cont)OUTDOOR SOUND POWER (TOTAL UNIT)LEGEND NOTE: The indoor sound power is available in Bryant’s Electronic Catalogprogram (ECAT
133PERFORMANCE DATA (cont)Perfect Humidity™ Adaptive Dehumidification Coil Pressure Drop(Subcooling and Reheat Modes of Operation)60005000400030002000
134PERFORMANCE DATA (cont)050010001500200025000.05" 0.15" 0.25"Static Pressure (in. wg)Flow in cubic feet per minute (cfm)3-6 Ton7 1/2
135PERFORMANCE DATA (cont)EVAPORATOR-FAN MOTOR PERFORMANCE — STANDARD MOTORLEGENDBhp — Brake Horsepower*Extensive motor and electrical testing on thes
136PERFORMANCE DATA (cont)POWER EXHAUST OPTIONS*Single or three phase rooftop unit.POWER EXHAUST POWER REQUIREMENTSLEGENDMOCP — Maximum Overcurrent Pr
137ELECTRICAL DATA581B036-150 UNITSUNIT SIZE581BNOMINALV-PH-HzIFMTYPECONV OUTLETVOLTAGE RANGECOMPRESSOR (each) OFM (each)IFM FLACOMBUSTIONFAN MOTORPOW
138ELECTRICAL DATA (cont)581B036-150 UNITSLEGEND*The values listed in this table do not include power exhaust. See table at right for powerexhaust req
139TYPICAL WIRING SCHEMATICS — 581BSIZES 036-150 (581B090, 460-3-60 Shown)a48-8233580F036-151 AND 581B036-150
14**ARI* CAPACITY RATINGS — 581C024-060 LEGEND*Air-Conditioning & Refrigeration Institute.**ARI does not require EER ratings f
140TYPICAL WIRING SCHEMATICS — 581B (cont)LEGENDIAQ — Indoor Air QualityLA — Low Ambient Lockout DevicePOT — PotentiometerOAT — Outdoor-Air Temperatur
141TYPICAL WIRING SCHEMATICS — 581B (cont)C2 FOR 008-014 UNITSLINE SIDEC1113232321BLUBLUGRAGRAREDGRAREDREDYELYEL208-230-1 ONLY240VH1H1H3H2H2H4TRAN4TR
142TYPICAL PIPING AND WIRING — 581B036-150NO.2NO.1CONVENIENCEOUTLETVertical Discharge DuctingHorizontal Discharge DuctingNEC — National Electrical Cod
143GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITHGAS HEAT — CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECI
144GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)2. Dual compressor models (size 090-150) shall haveface-split type evaporator coil (circui
145GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)The lockout protection shall be easily discon-nected at the control board, if necessary.b.
146GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)t. Remote Minimum Position Control — A field-installed accessory remote potentiometer allo
147GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)23. Return Air Enthalpy Sensor (EconoMi$er IV orEconoMi$er2):The return air enthalpy senso
148PHYSICAL DATA — 581CLEGENDUNIT SIZE 581C 024 036 048 060NOMINAL CAPACITY (tons)2 3 4 5 OPERATING WEIGHT(lb) Base Unit** 530 540 560 635 COMPR
149PHYSICAL DATA — 581CLEGENDUNIT SIZE 581C 024 036 048 060FURNACE SECTIONRollout Switch Cutout Temp(F)† 195 195 195 195Burner Orifice Diameter (in...
15HEATING CAPACITIES AND EFFICIENCIES — 581C024-060 (cont)208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx208/230/460/575-3-60 — 2-STAGE GAS HEATAFU
150BASE UNIT DIMENSIONS — 581C024-060581C024-060
151PERFORMANCE DATA — 581CCOOLING CAPACITIES — 581C024-060 STANDARD UNITS581C024 (2 Tons)Temp (F) Air Entering Evaporator -- CFM/BFAir Ent 600/0.12 80
152PERFORMANCE DATA — 581CCOOLING CAPACITIES — 581C024-060 STANDARD UNITS (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate
153PERFORMANCE DATA — 581CFAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied d
154PERFORMANCE DATA — 581CLEGEND*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.Refer to page 107 for general Fan Pe
155PERFORMANCE DATA — 581CLEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.Refer to page 107 for general Fan P
156PERFORMANCE DATA — 581CLEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.Refer to page 107 for general Fan Pe
157PERFORMANCE DATA — 581CFAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
158PERFORMANCE DATA — 581CLEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.See page 107 for general fan perfor
159PERFORMANCE DATA — 581CLEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive. See page 107 for general fan perfo
16ARI* CAPACITY RATINGS — 579F180-300LOW HEAT UNITSHIGH HEAT UNITSLEGEND*Air Conditioning and Refrigeration Institute.NOTES:1. Rated in accordance wit
160PERFORMANCE DATA — 581CLEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.See page 107 for general fan perform
161PERFORMANCE DATA — 581CFAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581C024-060*Approximate fan rpm shown (standard motor/drive).FAN RPM
162EVAPORATOR-FAN MOTOR EFFICIENCY — 581C024-060*Single phase/3 phase.NOTES:1. Convert bhp to watts using the following formula:2. The EPACT (Energy P
163PERFORMANCE DATA — 581CALTITUDE COMPENSATION* — 581C024-060STANDARD UNIT*As the height above sea level increases, there is less oxygen per cubicfoo
164PERFORMANCE DATA — 581C* Single or three phase rooftop unit.Vertical - Mounted in Economizer HoodPower Exhaust Part No. Power Exhaust DescriptionAp
165SOUND DATALEGENDARI — Air Conditioning and Refrigeration InstituteNOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECA
166PERFORMANCE DATA — 581C581C048-060 UNITSLEGEND*The values listed in this table do not include power exhaust. See table at rightfor power exhaust re
167TYPICAL WIRING SCHEMATICS — 581CLEGENDOFM — Outdoor (Condenser) Fan MotorOLR — Overload RelayP—PlugPL — Plug AssemblyQT — Quadruple TerminalRS — Ro
168TYPICAL WIRING SCHEMATICS — 581CECONOMI$ER2 WIRING — 581C024-060 UNITNOTES:1. Switch on actuator must be in run position for economizer to operate.
169TYPICAL PIPING AND WIRING — 581C 024-060NO.2NO.1CONVENIENCEOUTLET NEC — National Electrical CodeHORIZONTAL DISCHARGE DUCTINGVERTICAL DISCHARGE DUCT
17ARI* CAPACITY RATINGS — 580F180-300LEGEND*Air Conditioning and Refrigeration Institute.NOTES:1. Rated in accordance with ARI Standards 360 and 270.2
170GUIDE SPECIFICATONS — 581C024-060Packaged Rooftop Electric Cooling Unit with Gas Heat –Constant Volume ApplicationHVAC Guide SpecificationsSize Ran
171GUIDE SPECIFICATIONS — 581C024-060 (cont)2. Testing:a. Evaporator and condenser coils shall be quali-fied to UL 1995 burst test at 2,200 psi.b. Eva
172GUIDE SPECIFICATIONS — 581C024-060 (cont)The lockout protection shall be easily discon-nected at the control board, if necessary.b. Heating section
173GUIDE SPECIFICATIONS — 581C024-060 (cont)3. Manual Outdoor-Air Damper:Manual damper package shall consist of damper,birdscreen, and rainhood which
174GUIDE SPECIFICATIONS — 581C024-060 (cont)For the EconoMi$er2, the power exhaust shall becontrolled by the or third party controls.23. Outdoor Air E
175PHYSICAL DATA — 579F180-300LEGEND*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora-tor coils; and Circuit 2 uses the
176PHYSICAL DATA — 579F180-300 (cont)LEGEND*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora-tor coils; and Circuit 2 u
177BASE UNIT DIMENSIONS — 579F180,216NOTES:1. Refer to print for roof curb accessory dimensions.2. Dimensions in ( ) are in millimeters.3. Center of G
178BASE UNIT DIMENSIONS — 579F240,300NOTES:1. Refer to print for roof curb accessory dimensions.2. Dimensions in ( ) are in millimeters.3. Center of G
179ACCESSORY DIMENSIONS — 579F180-300Horizontal and Vertical Roof Curbs — 579F180-300PKG. NO. REF.CURBHEIGHTDESCRIPTIONCRRFCURB010A00 1′− 2″ (305) Sta
18ARI* CAPACITY RATINGS — 581A155,180LOW HEAT UNITSHIGH HEAT UNITSLEGEND*Air Conditioning and Refrigeration Institute.NOTES:1. Rated in accordance wit
180ACCESSORY DIMENSIONS — 579F180-300 (cont)Horizontal Supply/Return Adapter Installation (579F180-300)NOTE: CRRFCURB013A00 is a fully factory preasse
181ACCESSORY DIMENSIONS (cont)Factory-Installed Convenience OutletFactory-Installed Non-Fused DisconnectLEGENDK.O. — Knockouta48-4184a48-4185579F180-3
182SELECTION PROCEDURE (With 579F180 Example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity . . .
183PERFORMANCE DATA — 579FCOOLING CAPACITIESLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be us
184PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
185PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
186PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
187PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
188PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
189PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
19ARI* CAPACITY RATINGS — 581A210-300LEGEND*Air Conditioning and Refrigeration Institute.†IPLV values are calculated based on control configuration T.
190PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form
191PERFORMANCE DATA — 579F (cont)FAN PERFORMANCE — 579F180-300 UNITS LEGEND*Standard low-medium static drive range is 891 to 1179 rpm (208/
192PERFORMANCE DATA — 579F (cont)FAN PERFORMANCE — 579F180-300 UNITS (cont) LEGEND*Standard low-medium static drive range is 1066 to 12
193PERFORMANCE DATA — 579F (cont)FAN PERFORMANCE — 579F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range for the 216 size is 910 to 10
194PERFORMANCE DATA — 579F (cont)ALTITUDE COMPENSATION* —579F180-300*Includes a 4% input reduction per each 1,000 feet.†Orifices available through you
195PERFORMANCE DATA — 579F (cont)ALTITUDE COMPENSATION — 579F180-300(LP Gas Units)OUTDOOR SOUND POWERNOTE: Indoor sound power is available in Bryant’s
196PERFORMANCE DATA — 579F (cont)EVAPORATOR-FAN MOTOR DATALEGEND*Extensive motor and electrical testing on these units ensures that the full horsepowe
197ELECTRICAL DATA LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements for multimotor and combi
198TYPICAL WIRING SCHEMATICS — 579F(579F240, 208/230 V Shown)a48-7929
199TYPICAL WIRING SCHEMATICS — 579F(579F240, 208/230 V Shown) (cont)AHA — Adjustable Heat AnticipatorBKR W/AT — Breaker with Amp TurnsC—Contactor, Com
2TABLE OF CONTENTSPageFeatures/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Model Number Nomenclature . . . . . . . .
20OPTIONS AND ACCESSORIES581C024-060, 581B036-150 AND 580F036-151*Factory-installed.†Field-installed.NOTES: 1. Refer to unit price pages or contact yo
200TYPICAL WIRING SCHEMATICS — 579F (cont)435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUG
201TYPICAL WIRING SCHEMATICS — 579F (cont)Non-Fused Disconnect (Optional) — 579F180-300NOTES:1. If the Non-Fused Disconnect Service Option is ordered
202TYPICAL PIPING AND WIRING — 579F180-300(579F180 Shown)LEGENDNEC — National Electrical Codeb48-1258
203PHYSICAL DATA — 580F180-300LEGEND*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;and Circuit 2 us
204PHYSICAL DATA — 580F180-300 (cont)LEGEND*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;and Circu
205BASE UNIT DIMENSIONS — 580F180, 210$a48-8203580F180-300
206BASE UNIT DIMENSIONS — 580F240a48-8204
207BASE UNIT DIMENSIONS — 580F300$a48-8205580F180-300
208ACCESSORY DIMENSIONS — 580F180-240Horizontal and Vertical Roof Curbs580F180-240PKG. NO. REF.CURBHEIGHTDESCRIPTIONCRRFCURB010A00 1′− 2″ (305) Standa
209ACCESSORY DIMENSIONS — 580F300Vertical Roof Curbs580F300a48-7456580F180-300
21OPTIONS AND ACCESSORIES (cont)579F180-300, 580F180-300, AND 581A155-180*Factory-installed.†Field-installed.NOTES: 1. Refer to unit price pages or co
210ACCESSORY DIMENSIONS — 580F (cont)Horizontal Supply/Return Adapter Installation (580F180-240)NOTE: CRRFCURB013A00 is a fully factory preassembled h
211ACCESSORY DIMENSIONS — 580F (cont)Factory-Installed Convenience OutletFactory-Installed Non-Fused Disconnect (180-300)LEGENDK.O. — Knockouta48-4184
212SELECTION PROCEDURE (With 580F240 Example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity . . .
213PERFORMANCE DATACOOLING CAPACITIES LEGEND580F180 (15 TONS) Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator —
214PERFORMANCE DATA (cont)COOLING CAPACITIES (cont) LEGEND580F240 (20 TONS) Temp (F)Air EnteringCondenser(Edb)Air Enterin
215PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITSLEGEND*Standard low-medium static drive range is 873 to 1021 rpm. Alternatehigh-static dr
216PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range is 873 to 1021 rpm. Alternatehigh-st
217PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont) LEGEND *Standard low-medium static drive range is 910 to 1095 rpm. Alt
218PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range is 1002 to 1151 rpm. Alternatehigh-s
219PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range is 1002 to 1151 rpm. Alternatehigh-s
22OPTIONS AND ACCESSORIES (cont)581A210-300*Factory-installed.†Field-installed.NOTES: 1. Refer to unit price pages or contact your local representativ
220PERFORMANCE DATA (cont)\FAN PERFORMANCE — 580F180-300 UNITS (cont) LEGEND*Standard low-medium static drive range is 1066 to 1283 rpm
221PERFORMANCE DATA (cont)ALTITUDE COMPENSATION* —580F180-300*Includes a 4% input reduction per each 1,000 feet.†Orifices available through your Bryan
222PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300LEGEND*The static pressure must be added to external static pressure.
223ELECTRICAL DATA LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements for multimotor and combin
224TYPICAL WIRING SCHEMATICS — 580FTypical Wiring Schematic — 580F180, 460-3-60 ShownLEGENDAHA — Adjustable Heat AnticipatorC—Contactor, CompressorCAP
225TYPICAL WIRING SCHEMATICS — 580F (cont)435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUG
226TYPICAL WIRING SCHEMATICS — 580F (cont)Non-Fused Disconnect (Optional) — 580F180-300NOTES:1. If the Non-Fused Disconnect Service Option is ordered
227TYPICAL PIPING AND WIRING — 580F180-300LEGENDNEC — National Electrical Codeb48-1258580F180-300
228PHYSICAL DATA — 581A155,180 LEGEND *Evaporator coil fin material/condenser coil fin material.†Weight of 14-in. roof curb.**Ci
229PHYSICAL DATA — 581A210-300 LEGENDUNIT 581A 210 240 300NOMINAL CAPACITY (tons) 18 20 25OPERATING WEIGHT (lb)Al/Al 22242272252
23OPTIONS AND ACCESSORIES (cont)Roof Curbs (Horizontal and Vertical) permit installation andsecuring of ductwork to curb prior to mounting unit on the
230PHYSICAL DATA (cont)EVAPORATOR FAN DATA — 581A210-300 VERTICAL SUPPLY/RETURN UNITS LEGENDEVAPORATOR FAN DATA — 581A210-300 HORIZONTAL
231PHYSICAL DATA (cont) OPERATING AND RIGGING WEIGHTS — 581A155,180*Base unit weight does not include electric heaters, copper co
232BASE UNIT DIMENSIONS — 581A155,180UNIT581ASTD UNITWEIGHTECONOMI$ER IVWEIGHTCORNERACORNERBCORNERCCORNERDDIM A DIM B DIM CLb Kg Lb Kg Lb Kg Lb Kg Lb
233BASE UNIT DIMENSIONS — 581A210-300a48-8206581A155, 180
234ACCESSORY DIMENSIONS — 581A155,180PKG. NO. REF. CURB HEIGHT DESCRIPTIONCRRFCURB010A00 1′-2″ (305) Standard Curb 14″ HighCRRFCURB011A00 2′-0″ (610)S
235ACCESSORY DIMENSIONS (cont)Horizontal Supply/Return Adapter Installation (581A155,180)NOTE: CRRFCURB013A00 is a fully factory preassembled horizont
236ACCESSORY DIMENSIONS (cont)Factory-Installed Convenience OutletFactory-Installed Non-Fused Disconnecta48-4184a48-6126
237ACCESSORY DIMENSIONS — 581A210-300a48-8234581A155, 180
238SELECTION PROCEDUREI DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Gross CoolingCapacity (TC) . . . . . . . . . .
239PERFORMANCE DATACOOLING CAPACITIES — STANDARD UNITS LEGENDNOTES:1. Direct interpolation is permissible. Do not extrap
24PHYSICAL DATA — 580F036-073 LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-sentative for detai
240PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is permissible.
241581A155, 180PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is
242PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is permissible.
243PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is permissible.
244PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION LEGENDNOTES:1. Direct interpolation is permi
245PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i
246PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i
247PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i
248PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i
249PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND*Standard low-medium static drive range is 895 to 1147 rpm. Other rpms requi
25PHYSICAL DATA — 580F036-073 (cont) LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-sentative fo
250PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard low-medium static drive range is 895 to 1147 rpm. Other rpm
251581A155-300PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard low-medium static drive range is 873 to 1021 rpm
252PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard low-medium static drive range is 873 to 1021 rpm. Alternate
253PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 647-886 (208/230 and 460-v), 810-1
254PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 647-886 (208/230 and 460-v), 810-1
255PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 647-886 (208/230 and 460-v), 810-1
256PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 949-1206High Range: 941-1176All ot
257581A155-300PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 949-1206High Range: 941
258PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 949-1206High Range: 941-1176All ot
259PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High Range: 941-1176All ot
26PHYSICAL DATA — 580F090,120,150 UNITS LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-sentati
260PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High Range: 941-1176All ot
261PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High Range: 941-1176All ot
262PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20
263PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20
264PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20
265581A155-300PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 8
266PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20
267PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20
268PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High
269PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High
27PHYSICAL DATA — 580F090,120,150 UNITS (cont) LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-s
270PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High
271PERFORMANCE DATA (cont)ALTITUDE COMPENSATION* — 581A155,180(Natural Gas Units)*Includes a 4% input reduction per each 1,000 feet.†Orifices availabl
272PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 581A155,180LEGEND *The static pressure must be added to external static pressure.
273PERFORMANCE DATA (cont)OUTDOOR SOUND POWER (TOTAL UNIT)LEGENDNOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECAT) fo
274PERFORMANCE DATA (cont)EVAPORATOR FAN MOTOR SPECIFICATIONS — 581A210-300LEGENDACCESSORY/FIOP STATIC PRESSURE (in. wg) — 581A210-300LEGEND *The stat
275ELECTRICAL DATA — 581A (cont)ELECTRICAL DATA — 581A155,180LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements for mult
276ELECTRICAL DATA — 581A (cont)ELECTRICAL DATA — 581A210-300 WITHOUT CONVENIENCE OUTLETLEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance wit
277ELECTRICAL DATA — 581A (cont)ELECTRICAL DATA — 581A210-300 WITH OPTIONAL CONVENIENCE OUTLETLEGEND*Fuse or HACR circuit breaker.NOTES:1. In complian
278TYPICAL WIRING SCHEMATICS — 581ALEGENDAHA — Adjustable Heat AnticipatorC—Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCC — Cooling Compe
279TYPICAL WIRING SCHEMATICS — 581A435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUGDIRECT
28PHYSICAL DATA — 580F091,103,121,151 UNITSASHRAE 90.1 COMPLIANT UNITS LEGEND *Evaporator coil fin material/condenser coil fin material. C
280TYPICAL PIPING AND WIRING — 581A (581A155 Shown)LEGENDNEC — National Electrical Codeb48-1258
281GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITSPACKAGED ROOFTOP ELECTRIC COOLING UNIT WITHGAS HEAT — CONSTANT VOLUME APPLICATION
282GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)3. Burners shall be of the in-shot type constructed ofaluminum-coated stee
283GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)2. Roof Curbs (Horizontal and Vertical):a. Formed of 16-gage galvanized st
284GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)11. Low-Ambient Kits:When used, allows units to operate at lower outdooram
285GUIDE SPECIFICATIONS — 581A210-300 UNITSPACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECIFICATIONS
286GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)3. Optional pre-coated aluminum-fin coils shall have adurable epoxy-phenolic coating to provide prot
287GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)M. Special Features:Certain features are not applicable when the featuresdesignated * are specified.
288GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)11. Non-Fused Disconnect Switch:Switch shall be factory-installed, internally mounted,NEC and UL app
289CONTROLSOPERATING SEQUENCE, SIZE 024-151 UNITSCooling, Units Without Economizer — When thermostat callsfor cooling, terminals G and Y1 are energize
29PHYSICAL DATA — 580F091,103,121,151 UNITS (cont)ASHRAE 90.1 COMPLIANT UNITS (cont) LEGEND *Evaporator coil fin material/condenser coil f
290CONTROLS (cont)Heating, Units Without Economizer — When the thermostatcalls for heating, power is sent to W on the IGC (integrated gasunit controll
291CONTROLS (cont)When the thermostat is satisfied and W1 and W2 are deener-gized, the IFM continues to run and the economizer damperthen moves to the
292CONTROLS (cont)If field-installed accessory CO2 sensors are connected to theEconoMi$er IV control, a demand controlled ventilation strategywill beg
293APPLICATION DATA1. CONDENSATE DRAIN PAN — A sloped condensate drainpan is supplied on all units. The condensate pan must beexternally trapped. Cond
294APPLICATION DATA (cont)c. E-COATED ALUMINUM FIN coils undergo a preciselycontrolled scientific process that bonds an impermeableepoxy coating to th
295APPLICATION DATA (cont)b. CONTROL FEATURES — The EconoMi$er IV controllerprovides superior functionality for rooftop unit operation.EconoMi$er IV c
296APPLICATION DATA (cont)ECONOMI$ER IV SENSOR USAGE CHART*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As suc
Copyright 2007 Bryant Heating & Cooling Systems Printed in U.S.A. 3/07 Catalog No. PDS580F-36-4SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT
3FEATURES/BENEFITS (cont)EASY INSTALLATION AND CONVERSIONAll Units are Shipped in the Vertical Duct Configuration forfit-up to standard roof curbs. Th
30BASE UNIT DIMENSIONS — 580F036-072a48-8195580F036-151
31BASE UNIT DIMENSIONS — 580F073a48-8196580F036-151
32BASE UNIT DIMENSIONS — 580F090,120,150a48-8197580F036-151
33BASE UNIT DIMENSIONS — 580F091,103,121,151a48-8198580F036-151
34ACCESSORY DIMENSIONS — 580FROOF CURBACCESSORYA UNIT SIZECRRFCURB001A011′-2″[356]580F036-073CRRFCURB002A012′-0″[610]NOTES:1. Roof curb accessory is s
35ACCESSORY DIMENSIONS — 580F (cont)CONNECTORPKG. ACCY.BCD ALT DRAIN HOLEGAS POWER CONTROLACCESSORY POWERCRBTMPWR001A012′-87/16″[827]1′-1015/16″[583]1
36SELECTION PROCEDURE (with 580F060 example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC). .
37PERFORMANCE DATACOOLING CAPACITIESStandard Ratings LEGENDNOTES:1. Direct interpolation is permissi
38PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)580F072 (6 TONS)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF1800/0.06 2100/0.0
39PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)580F091 (71/2 TONS)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF2250/0.10 2800/
4FEATURES/BENEFITS (cont)INDOOR-AIR QUALITY (IAQ) BEGINS WITH BRYANT ROOF-TOPS — Sloped condensate pans minimize biological growth inrooftop units in
40PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)Standard Ratings LEGENDNOTES:1. Direct interpolation is permissible. Do not
41PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS LEGEND See page 74 for general fan performance notes.
42PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance note
43PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance note
44PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1300 to 1685 rpm. All ot
45PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1070 to 1460 rpm. All oth
46PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 590 to 840 rpm. All other
47PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other
48PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All other
49PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other
5MODEL NUMBER NOMENCLATURE580F036-151 3 to 121/2 TonsNOTE: The example model number 580FEV090180KV designates a 7 1/2 ton 460-3-60 volt gas/electric r
50PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All other
51PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other
52PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 835 to 1085 rpm. All other
53PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All other
54PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other
55PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 835 to 1085 rpm. All other
56PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All other
57PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All other
58PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All other
59PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS LEGEND See page 74 for general fan performance notes.
6MODEL NUMBER NOMENCLATURE581B036-150 (Standard) 3 to 121/2 TonsNOTE: The example model number 581BEV090180HQ designates a 7 1/2 ton 460-3-60 volt gas
60PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance not
61PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance not
62PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1300 to 1685 rpm. All o
63PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1070 to 1460 rpm. All o
64PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 590 to 840 rpm. All othe
65PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All othe
66PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All oth
67PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All othe
68PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All oth
69PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All othe
7MODEL NUMBER NOMENCLATURE581C024-060 (Standard Efficiency) — 2 to 5 TonsNOTE: The example model number 581CEV060150HQ designates a 5 ton 460-3-60 vol
70PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 835 to 1085 rpm. All oth
71PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All oth
72PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All oth
73PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All oth
74PERFORMANCE DATA (cont)GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES1. Values include losses for filters, unit casing, and wet coils. See thispage f
75PERFORMANCE DATA (cont)FAN RPM AT MOTOR PULLEY SETTINGS* — 580F036-073*Approximate fan rpm shown.†Indicates alternate motor and drive package.**Indi
76PERFORMANCE DATA (cont)POWER EXHAUST OPTIONS VERTICAL — MOUNTED IN ECONOMIZER HOODPOWER EXHAUSTPART NO.POWER EXHAUST DESCRIPTIONAPPLICATION USAGEPOW
77PERFORMANCE DATA (cont)OPTIONAL POWER EXHAUSTPOWER REQUIREMENTSLEGENDEVAPORATOR-FAN MOTOR EFFICIENCY*Single phase/three-phase.NOTE: The EPACT (Ener
78PERFORMANCE DATA (cont)EVAPORATOR-FAN MOTOR PERFORMANCELEGENDBHP — Brake Horsepower*Extensive motor and electrical testing on these units ensures th
79ELECTRICAL DATA LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In compliance
8MODEL NUMBER NOMENCLATURE — 579F180-300MODEL NUMBER NOMENCLATURE580F180-300NOTES:1. All indoor-fan motors 5 hp and larger meet the minimum efficiency
80ELECTRICAL DATA (cont)UNIT SIZE580FNOMINALV-PH-HzIFM TYPECONV OUTLETVOLTAGE RANGECOMPRESSOR (each) OFM (each) IFM FLACOMBUSTIONFAN MOTORPOWER SUPP
81ELECTRICAL DATA (cont) LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In com
82ELECTRICAL DATA (cont) LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In com
83TYPICAL WIRING SCHEMATICS — 580F036-151(580F090, 460-3-60 Shown)CIRCUITBREAKERVOLTS MFG. PT. NO.MUST TRIPAMPSCB 24 VPOTTER & BRUMFIELD3.2W2BX-10
84TYPICAL WIRING SCHEMATICS — 580F036-151 (cont)LEGENDIAQ — Indoor Air QualityLA — Low Ambient Lockout DevicePOT — PotentiometerOAT — Outdoor-Air Temp
85TYPICAL WIRING SCHEMATICS — 580F (cont)C2 FOR 008-014 UNITSLINE SIDEC1113232321BLUBLUGRAGRAREDGRAREDREDYELYEL208-230-1 ONLY240VH1H1H3H2H2H4TRAN4TRA
86TYPICAL PIPING AND WIRING — 580F036-151NO.2NO.1CONVENIENCEOUTLETVertical Discharge DuctingHorizontal Discharge DuctingNEC — National Electrical Code
87PHYSICAL DATA — 581B036-072 LEGEND*Single phase/three phase.†Indicates automatic reset.**60,000 and 72,000 Btuh heat input units have 2
88PHYSICAL DATA — 581B036-072 (cont) LEGEND*Single phase/three phase.†Indicates automatic reset.**60,000 and 72,000 Btuh heat input units
89PHYSICAL DATA — 581B090-150 LEGEND*Single phase/three phase.†Indicates automatic reset.**72,000 Btuh heat input units have 2 burners.11
9MODEL NUMBER NOMENCLATURE581A155, 180, 181 — 13 to 15 TonsMODEL NUMBER NOMENCLATURE581A210-300 — 18 to 25 Tons*See pages 212 and 213 for cooling capa
90PHYSICAL DATA — 581B090-150 (cont) LEGEND*Single phase/three phase.†Indicates automatic reset.**180,000 Btuh heat input units have 2 bu
91BASE UNIT DIMENSIONS — 581B036-072a48-8199581B036-150
92BASE UNIT DIMENSIONS — 581B090-150UNIT581BSTD UNIT WEIGHTECONOMI$ER IVWEIGHTVERT. ECON IVW/P.E. WEIGHT(A)CORNER WEIGHT(B)CORNER WEIGHT(C)CORNER WEIG
93ACCESSORY DIMENSIONS — 581B036-072a48-8201581B036-150
94ACCESSORY DIMENSIONS — 581B090-150a48-8202581B036-150
95SELECTION PROCEDURE (With 581B048 Example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC) .
96PERFORMANCE DATACOOLING CAPACITIES, STANDARD UNITSStandard RatingsLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The foll
97PERFORMANCE DATA (cont)COOLING CAPACITIES, STANDARD UNITS (cont)Standard RatingsLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapola
98PERFORMANCE DATA (cont)COOLING CAPACITIES, STANDARD UNITS (cont)Standard RatingsLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapola
99PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTIONLEGENDNOTES:1. Direct interpolation