Form No. PDS580F-36-4
COMMERCIAL
SINGLE PACKAGE ROOFTOP UNITS
GAS HEATING/ELECTRIC COOLING UNITS
Standard efficiency units (580F072, 090, 120, 150 and
579F180-300) are available. Standard efficiency units
(580F036-060, 073, 091,103,121,151, and 180-300) that meet
ASHRAE 90.1-04 minimum energy efficiency requirements are
also available. High efficiency units (581C024-060, 581B036-
150 and 581A155-300) well exceed ASHRAE 90.1-04 energy
efficiency requirements and must comply with Energy Star high
efficiency requirements. Gas heating with electric cooling roof-
tops offer:
Pre-painted galvanized steel cabinet for long life and quality
appearance
Commercial strength base rails with built-in rigging capability
Convertible design for vertical or horizontal supply/return
(024-151 field convertible, factory supplied vertical supply/
return and 210-300 discrete configuration only)
Non-corrosive, sloped condensate drain pan, meets
ASHRAE 62 (IAQ)
Two-inch return-air filters
A wide assortment of factory-installed options available,
including high-static drives that provide additional perfor-
mance range
Factory-installed optional gear driven EconoMi$er IV (vertical
return for sizes 024-151 only) for use with standard rooftop
unit controls (includes CO
2
sensor control capability)
Factory-installed optional gear driven EconoMi$er2 (vertical
return only) for use with third party DDC controls (includes
4 to 20 mA actuator for demand control ventilation)
• Perfect Humidity™ dehumidification package (581C036-060
and 581B036-150 only)
Hot gas reheat dehumidification package (581A181-300 only)
Heat Options
Exclusive integrated gas control board with diagnostics
Alumagard™ heat exchanger coating
Induced-draft fan for gas combustion
Tubular, dimpled heat exchangers
Natural gas
LP conversion kits
Low NO
X
(size 024-060 only)
Optional type 409 stainless steel heat exchangers.
FEATURES/BENEFITS
Every compact one-piece unit arrives fully assembled,
charged, tested, and ready to run.
GAS HEAT MODELS — All ignition components are contained
in the compact IGC (integrated gas controller) which is easily
accessible for servicing. The IGC control board, designed and
manufactured exclusively for Bryant rooftop units, provides
built-in diagnostic capability. An LED (light-emitting diode) sim-
plifies troubleshooting by providing visual fault notification and
required system status confirmation.
The IGC also contains an exclusive anti-cycle protection for
gas heat operation. After 4 continuous cycles on the unit high-
temperature limit switch, the gas heat operation is disabled,
and an error code is issued. This feature greatly improves reli-
ability of the rooftop unit.
The IGC also contains burner control logic for accurate and
dependable gas ignition. The LED is visible without removing
the unit control box access panel. This LED fault-notification
system reduces service person troubleshooting time and mini-
mizes service costs. The IGC also maximizes heating effi-
ciency by controlling evaporator-fan on and off delays.
Tubular, dimpled gas heat exchangers optimize heat transfer
for improved efficiency. The tubular design permits hot gases
to make multiple passes across the path of the supply air. The
dimpled design creates a turbulent gas flow to maximize heat-
ing efficiency.
580F, 579F, 581A/B/C
DuraPac and
DuraPac Plus Series
Sizes 024-300
2 to 25 Tons
SIZES 024-073
SIZES 090-151
579F180-216
581A155,180
580F180,210
580F240
579F240-300
580F300
581A210-300
48-910df
a48-8207
50-1242f
50-1214df
a48-5997
48-831df
Vista de página 0
1 2 3 4 5 6 ... 297 298

Resumo do Conteúdo

Página 1 - DuraPac Plus Series

Form No. PDS580F-36-4COMMERCIALSINGLE PACKAGE ROOFTOP UNITSGAS HEATING/ELECTRIC COOLING UNITSStandard efficiency units (580F072, 090, 120, 150 and579F

Página 2 - FEATURES/BENEFITS (cont)

10ARI* CAPACITY RATINGS — 580F036-151 LEGEND*Air Conditioning and Refrigeration Institute.†Applies only to units with capa

Página 3

100PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in

Página 4

101PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in

Página 5

102PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in

Página 6

103PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in

Página 7 - MODEL NUMBER NOMENCLATURE

104PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGENDNOTES:1. Direct interp

Página 8

105PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in

Página 9 - 581A210-300 — 18 to 25 Tons

106PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)LEGEND*Negative SHC value in

Página 10

107PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied d

Página 11 - ARI* CAPACITY RATINGS (cont)

108PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 770 to 1185 rpm. All other rpms require field-sup

Página 12 - Sizes 150

109PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-su

Página 13

11ARI* CAPACITY RATINGS (cont)HEATING CAPACITIES AND EFFICIENCIES (Standard Efficiency Units) — 580F036-151 (cont)208/230/460-3-60 — SINGLE-STAGE GAS

Página 14

110PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-su

Página 15

111PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-su

Página 16 - OPERATING LIMITS (F)

112PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All othe

Página 17

113PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All othe

Página 18 - AIR QUANTITY LIMITS (Cooling)

114PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All othe

Página 19 - HORIZONTAL SUPPLY — PROPANE

115PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All othe

Página 20 - OPTIONS AND ACCESSORIES

116PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All othe

Página 21

117PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All othe

Página 22 - 581A210-300

118PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All othe

Página 23 - 580F036-151

119PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field- sup

Página 24 - PHYSICAL DATA — 580F036-073

12ARI* CAPACITY RATINGS — 581B036-150 LEGEND*Air-Conditioning & Refrigeration Institute.†Applies only to units with capaci

Página 25

120PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 770 to 1185 rpm. All other rpms require field-s

Página 26

121PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-

Página 27

122PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-

Página 28

123PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1686 rpm. All other rpms require field-

Página 29

124PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All ot

Página 30

125PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All ot

Página 31

126PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 840 to 1085 rpm. All ot

Página 32

127PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All ot

Página 33

128PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All ot

Página 34 - ACCESSORY DIMENSIONS — 580F

129PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All ot

Página 35

13ARI* CAPACITY RATINGS (cont)HEATING CAPACITIES AND EFFICIENCIES — 581B036-150(cont)208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx208/230/460-3-6

Página 36

130PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All ot

Página 37

131PERFORMANCE DATA (cont)FAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581B036-150*Approximate fan rpm shown (standard motor/drive).FAN RPM

Página 38

132PERFORMANCE DATA (cont)OUTDOOR SOUND POWER (TOTAL UNIT)LEGEND NOTE: The indoor sound power is available in Bryant’s Electronic Catalogprogram (ECAT

Página 39

133PERFORMANCE DATA (cont)Perfect Humidity™ Adaptive Dehumidification Coil Pressure Drop(Subcooling and Reheat Modes of Operation)60005000400030002000

Página 40

134PERFORMANCE DATA (cont)050010001500200025000.05" 0.15" 0.25"Static Pressure (in. wg)Flow in cubic feet per minute (cfm)3-6 Ton7 1/2

Página 41

135PERFORMANCE DATA (cont)EVAPORATOR-FAN MOTOR PERFORMANCE — STANDARD MOTORLEGENDBhp — Brake Horsepower*Extensive motor and electrical testing on thes

Página 42

136PERFORMANCE DATA (cont)POWER EXHAUST OPTIONS*Single or three phase rooftop unit.POWER EXHAUST POWER REQUIREMENTSLEGENDMOCP — Maximum Overcurrent Pr

Página 43

137ELECTRICAL DATA581B036-150 UNITSUNIT SIZE581BNOMINALV-PH-HzIFMTYPECONV OUTLETVOLTAGE RANGECOMPRESSOR (each) OFM (each)IFM FLACOMBUSTIONFAN MOTORPOW

Página 44

138ELECTRICAL DATA (cont)581B036-150 UNITSLEGEND*The values listed in this table do not include power exhaust. See table at right for powerexhaust req

Página 45

139TYPICAL WIRING SCHEMATICS — 581BSIZES 036-150 (581B090, 460-3-60 Shown)a48-8233580F036-151 AND 581B036-150

Página 46

14**ARI* CAPACITY RATINGS — 581C024-060 LEGEND*Air-Conditioning & Refrigeration Institute.**ARI does not require EER ratings f

Página 47

140TYPICAL WIRING SCHEMATICS — 581B (cont)LEGENDIAQ — Indoor Air QualityLA — Low Ambient Lockout DevicePOT — PotentiometerOAT — Outdoor-Air Temperatur

Página 48

141TYPICAL WIRING SCHEMATICS — 581B (cont)C2 FOR 008-014 UNITSLINE SIDEC1113232321BLUBLUGRAGRAREDGRAREDREDYELYEL208-230-1 ONLY240VH1H1H3H2H2H4TRAN4TR

Página 49

142TYPICAL PIPING AND WIRING — 581B036-150NO.2NO.1CONVENIENCEOUTLETVertical Discharge DuctingHorizontal Discharge DuctingNEC — National Electrical Cod

Página 50

143GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150PACKAGED ROOFTOP ELECTRIC COOLING UNIT WITHGAS HEAT — CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECI

Página 51

144GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)2. Dual compressor models (size 090-150) shall haveface-split type evaporator coil (circui

Página 52

145GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)The lockout protection shall be easily discon-nected at the control board, if necessary.b.

Página 53

146GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)t. Remote Minimum Position Control — A field-installed accessory remote potentiometer allo

Página 54

147GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)23. Return Air Enthalpy Sensor (EconoMi$er IV orEconoMi$er2):The return air enthalpy senso

Página 55

148PHYSICAL DATA — 581CLEGENDUNIT SIZE 581C 024 036 048 060NOMINAL CAPACITY (tons)2 3 4 5 OPERATING WEIGHT(lb) Base Unit** 530 540 560 635 COMPR

Página 56

149PHYSICAL DATA — 581CLEGENDUNIT SIZE 581C 024 036 048 060FURNACE SECTIONRollout Switch Cutout Temp(F)† 195 195 195 195Burner Orifice Diameter (in...

Página 57

15HEATING CAPACITIES AND EFFICIENCIES — 581C024-060 (cont)208/230/460-3-60 — SINGLE-STAGE GAS HEAT — LOW NOx208/230/460/575-3-60 — 2-STAGE GAS HEATAFU

Página 58

150BASE UNIT DIMENSIONS — 581C024-060581C024-060

Página 59

151PERFORMANCE DATA — 581CCOOLING CAPACITIES — 581C024-060 STANDARD UNITS581C024 (2 Tons)Temp (F) Air Entering Evaporator -- CFM/BFAir Ent 600/0.12 80

Página 60

152PERFORMANCE DATA — 581CCOOLING CAPACITIES — 581C024-060 STANDARD UNITS (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate

Página 61 - Watts — Input Watts to Motor

153PERFORMANCE DATA — 581CFAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied d

Página 62

154PERFORMANCE DATA — 581CLEGEND*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.Refer to page 107 for general Fan Pe

Página 63

155PERFORMANCE DATA — 581CLEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.Refer to page 107 for general Fan P

Página 64

156PERFORMANCE DATA — 581CLEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.Refer to page 107 for general Fan Pe

Página 65

157PERFORMANCE DATA — 581CFAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGEND*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied

Página 66

158PERFORMANCE DATA — 581CLEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive.See page 107 for general fan perfor

Página 67

159PERFORMANCE DATA — 581CLEGEND *Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied drive. See page 107 for general fan perfo

Página 68

16ARI* CAPACITY RATINGS — 579F180-300LOW HEAT UNITSHIGH HEAT UNITSLEGEND*Air Conditioning and Refrigeration Institute.NOTES:1. Rated in accordance wit

Página 69

160PERFORMANCE DATA — 581CLEGEND*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied drive.See page 107 for general fan perform

Página 70

161PERFORMANCE DATA — 581CFAN RPM AT MOTOR PULLEY SETTING WITH STANDARD MOTOR* — 581C024-060*Approximate fan rpm shown (standard motor/drive).FAN RPM

Página 71

162EVAPORATOR-FAN MOTOR EFFICIENCY — 581C024-060*Single phase/3 phase.NOTES:1. Convert bhp to watts using the following formula:2. The EPACT (Energy P

Página 72

163PERFORMANCE DATA — 581CALTITUDE COMPENSATION* — 581C024-060STANDARD UNIT*As the height above sea level increases, there is less oxygen per cubicfoo

Página 73

164PERFORMANCE DATA — 581C* Single or three phase rooftop unit.Vertical - Mounted in Economizer HoodPower Exhaust Part No. Power Exhaust DescriptionAp

Página 74

165SOUND DATALEGENDARI — Air Conditioning and Refrigeration InstituteNOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECA

Página 75

166PERFORMANCE DATA — 581C581C048-060 UNITSLEGEND*The values listed in this table do not include power exhaust. See table at rightfor power exhaust re

Página 76

167TYPICAL WIRING SCHEMATICS — 581CLEGENDOFM — Outdoor (Condenser) Fan MotorOLR — Overload RelayP—PlugPL — Plug AssemblyQT — Quadruple TerminalRS — Ro

Página 77

168TYPICAL WIRING SCHEMATICS — 581CECONOMI$ER2 WIRING — 581C024-060 UNITNOTES:1. Switch on actuator must be in run position for economizer to operate.

Página 78

169TYPICAL PIPING AND WIRING — 581C 024-060NO.2NO.1CONVENIENCEOUTLET NEC — National Electrical CodeHORIZONTAL DISCHARGE DUCTINGVERTICAL DISCHARGE DUCT

Página 79

17ARI* CAPACITY RATINGS — 580F180-300LEGEND*Air Conditioning and Refrigeration Institute.NOTES:1. Rated in accordance with ARI Standards 360 and 270.2

Página 80

170GUIDE SPECIFICATONS — 581C024-060Packaged Rooftop Electric Cooling Unit with Gas Heat –Constant Volume ApplicationHVAC Guide SpecificationsSize Ran

Página 81

171GUIDE SPECIFICATIONS — 581C024-060 (cont)2. Testing:a. Evaporator and condenser coils shall be quali-fied to UL 1995 burst test at 2,200 psi.b. Eva

Página 82

172GUIDE SPECIFICATIONS — 581C024-060 (cont)The lockout protection shall be easily discon-nected at the control board, if necessary.b. Heating section

Página 83 - (580F090, 460-3-60 Shown)

173GUIDE SPECIFICATIONS — 581C024-060 (cont)3. Manual Outdoor-Air Damper:Manual damper package shall consist of damper,birdscreen, and rainhood which

Página 84

174GUIDE SPECIFICATIONS — 581C024-060 (cont)For the EconoMi$er2, the power exhaust shall becontrolled by the or third party controls.23. Outdoor Air E

Página 85

175PHYSICAL DATA — 579F180-300LEGEND*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora-tor coils; and Circuit 2 uses the

Página 86

176PHYSICAL DATA — 579F180-300 (cont)LEGEND*Circuit 1 uses the lower portion of condenser coil and lower portion of evapora-tor coils; and Circuit 2 u

Página 87 - PHYSICAL DATA — 581B036-072

177BASE UNIT DIMENSIONS — 579F180,216NOTES:1. Refer to print for roof curb accessory dimensions.2. Dimensions in ( ) are in millimeters.3. Center of G

Página 88

178BASE UNIT DIMENSIONS — 579F240,300NOTES:1. Refer to print for roof curb accessory dimensions.2. Dimensions in ( ) are in millimeters.3. Center of G

Página 89 - PHYSICAL DATA — 581B090-150

179ACCESSORY DIMENSIONS — 579F180-300Horizontal and Vertical Roof Curbs — 579F180-300PKG. NO. REF.CURBHEIGHTDESCRIPTIONCRRFCURB010A00 1′− 2″ (305) Sta

Página 90

18ARI* CAPACITY RATINGS — 581A155,180LOW HEAT UNITSHIGH HEAT UNITSLEGEND*Air Conditioning and Refrigeration Institute.NOTES:1. Rated in accordance wit

Página 91

180ACCESSORY DIMENSIONS — 579F180-300 (cont)Horizontal Supply/Return Adapter Installation (579F180-300)NOTE: CRRFCURB013A00 is a fully factory preasse

Página 92

181ACCESSORY DIMENSIONS (cont)Factory-Installed Convenience OutletFactory-Installed Non-Fused DisconnectLEGENDK.O. — Knockouta48-4184a48-4185579F180-3

Página 93

182SELECTION PROCEDURE (With 579F180 Example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity . . .

Página 94

183PERFORMANCE DATA — 579FCOOLING CAPACITIESLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be us

Página 95

184PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 96

185PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 97

186PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 98

187PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 99

188PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 100 - 581B036-150

189PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 101

19ARI* CAPACITY RATINGS — 581A210-300LEGEND*Air Conditioning and Refrigeration Institute.†IPLV values are calculated based on control configuration T.

Página 102

190PERFORMANCE DATA — 579F (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following form

Página 103

191PERFORMANCE DATA — 579F (cont)FAN PERFORMANCE — 579F180-300 UNITS LEGEND*Standard low-medium static drive range is 891 to 1179 rpm (208/

Página 104

192PERFORMANCE DATA — 579F (cont)FAN PERFORMANCE — 579F180-300 UNITS (cont) LEGEND*Standard low-medium static drive range is 1066 to 12

Página 105

193PERFORMANCE DATA — 579F (cont)FAN PERFORMANCE — 579F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range for the 216 size is 910 to 10

Página 106

194PERFORMANCE DATA — 579F (cont)ALTITUDE COMPENSATION* —579F180-300*Includes a 4% input reduction per each 1,000 feet.†Orifices available through you

Página 107

195PERFORMANCE DATA — 579F (cont)ALTITUDE COMPENSATION — 579F180-300(LP Gas Units)OUTDOOR SOUND POWERNOTE: Indoor sound power is available in Bryant’s

Página 108

196PERFORMANCE DATA — 579F (cont)EVAPORATOR-FAN MOTOR DATALEGEND*Extensive motor and electrical testing on these units ensures that the full horsepowe

Página 109

197ELECTRICAL DATA LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements for multimotor and combi

Página 110

198TYPICAL WIRING SCHEMATICS — 579F(579F240, 208/230 V Shown)a48-7929

Página 111

199TYPICAL WIRING SCHEMATICS — 579F(579F240, 208/230 V Shown) (cont)AHA — Adjustable Heat AnticipatorBKR W/AT — Breaker with Amp TurnsC—Contactor, Com

Página 112

2TABLE OF CONTENTSPageFeatures/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4Model Number Nomenclature . . . . . . . .

Página 113

20OPTIONS AND ACCESSORIES581C024-060, 581B036-150 AND 580F036-151*Factory-installed.†Field-installed.NOTES: 1. Refer to unit price pages or contact yo

Página 114

200TYPICAL WIRING SCHEMATICS — 579F (cont)435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUG

Página 115

201TYPICAL WIRING SCHEMATICS — 579F (cont)Non-Fused Disconnect (Optional) — 579F180-300NOTES:1. If the Non-Fused Disconnect Service Option is ordered

Página 116

202TYPICAL PIPING AND WIRING — 579F180-300(579F180 Shown)LEGENDNEC — National Electrical Codeb48-1258

Página 117

203PHYSICAL DATA — 580F180-300LEGEND*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;and Circuit 2 us

Página 118

204PHYSICAL DATA — 580F180-300 (cont)LEGEND*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils;and Circu

Página 119

205BASE UNIT DIMENSIONS — 580F180, 210$a48-8203580F180-300

Página 120

206BASE UNIT DIMENSIONS — 580F240a48-8204

Página 121

207BASE UNIT DIMENSIONS — 580F300$a48-8205580F180-300

Página 122

208ACCESSORY DIMENSIONS — 580F180-240Horizontal and Vertical Roof Curbs580F180-240PKG. NO. REF.CURBHEIGHTDESCRIPTIONCRRFCURB010A00 1′− 2″ (305) Standa

Página 123

209ACCESSORY DIMENSIONS — 580F300Vertical Roof Curbs580F300a48-7456580F180-300

Página 124

21OPTIONS AND ACCESSORIES (cont)579F180-300, 580F180-300, AND 581A155-180*Factory-installed.†Field-installed.NOTES: 1. Refer to unit price pages or co

Página 125

210ACCESSORY DIMENSIONS — 580F (cont)Horizontal Supply/Return Adapter Installation (580F180-240)NOTE: CRRFCURB013A00 is a fully factory preassembled h

Página 126

211ACCESSORY DIMENSIONS — 580F (cont)Factory-Installed Convenience OutletFactory-Installed Non-Fused Disconnect (180-300)LEGENDK.O. — Knockouta48-4184

Página 127

212SELECTION PROCEDURE (With 580F240 Example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity . . .

Página 128

213PERFORMANCE DATACOOLING CAPACITIES LEGEND580F180 (15 TONS) Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator —

Página 129

214PERFORMANCE DATA (cont)COOLING CAPACITIES (cont) LEGEND580F240 (20 TONS) Temp (F)Air EnteringCondenser(Edb)Air Enterin

Página 130

215PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITSLEGEND*Standard low-medium static drive range is 873 to 1021 rpm. Alternatehigh-static dr

Página 131

216PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range is 873 to 1021 rpm. Alternatehigh-st

Página 132

217PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont) LEGEND *Standard low-medium static drive range is 910 to 1095 rpm. Alt

Página 133

218PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range is 1002 to 1151 rpm. Alternatehigh-s

Página 134

219PERFORMANCE DATA (cont)FAN PERFORMANCE — 580F180-300 UNITS (cont)LEGEND*Standard low-medium static drive range is 1002 to 1151 rpm. Alternatehigh-s

Página 135

22OPTIONS AND ACCESSORIES (cont)581A210-300*Factory-installed.†Field-installed.NOTES: 1. Refer to unit price pages or contact your local representativ

Página 136

220PERFORMANCE DATA (cont)\FAN PERFORMANCE — 580F180-300 UNITS (cont) LEGEND*Standard low-medium static drive range is 1066 to 1283 rpm

Página 137 - 580F036-151 AND 581B036-150

221PERFORMANCE DATA (cont)ALTITUDE COMPENSATION* —580F180-300*Includes a 4% input reduction per each 1,000 feet.†Orifices available through your Bryan

Página 138 - ELECTRICAL DATA (cont)

222PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300LEGEND*The static pressure must be added to external static pressure.

Página 139

223ELECTRICAL DATA LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements for multimotor and combin

Página 140

224TYPICAL WIRING SCHEMATICS — 580FTypical Wiring Schematic — 580F180, 460-3-60 ShownLEGENDAHA — Adjustable Heat AnticipatorC—Contactor, CompressorCAP

Página 141

225TYPICAL WIRING SCHEMATICS — 580F (cont)435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUG

Página 142

226TYPICAL WIRING SCHEMATICS — 580F (cont)Non-Fused Disconnect (Optional) — 580F180-300NOTES:1. If the Non-Fused Disconnect Service Option is ordered

Página 143 - ENERGY STAR QUALIFIED

227TYPICAL PIPING AND WIRING — 580F180-300LEGENDNEC — National Electrical Codeb48-1258580F180-300

Página 144

228PHYSICAL DATA — 581A155,180 LEGEND *Evaporator coil fin material/condenser coil fin material.†Weight of 14-in. roof curb.**Ci

Página 145

229PHYSICAL DATA — 581A210-300 LEGENDUNIT 581A 210 240 300NOMINAL CAPACITY (tons) 18 20 25OPERATING WEIGHT (lb)Al/Al 22242272252

Página 146

23OPTIONS AND ACCESSORIES (cont)Roof Curbs (Horizontal and Vertical) permit installation andsecuring of ductwork to curb prior to mounting unit on the

Página 147

230PHYSICAL DATA (cont)EVAPORATOR FAN DATA — 581A210-300 VERTICAL SUPPLY/RETURN UNITS LEGENDEVAPORATOR FAN DATA — 581A210-300 HORIZONTAL

Página 148 - 581C024-060

231PHYSICAL DATA (cont) OPERATING AND RIGGING WEIGHTS — 581A155,180*Base unit weight does not include electric heaters, copper co

Página 149

232BASE UNIT DIMENSIONS — 581A155,180UNIT581ASTD UNITWEIGHTECONOMI$ER IVWEIGHTCORNERACORNERBCORNERCCORNERDDIM A DIM B DIM CLb Kg Lb Kg Lb Kg Lb Kg Lb

Página 150

233BASE UNIT DIMENSIONS — 581A210-300a48-8206581A155, 180

Página 151 - PERFORMANCE DATA — 581C

234ACCESSORY DIMENSIONS — 581A155,180PKG. NO. REF. CURB HEIGHT DESCRIPTIONCRRFCURB010A00 1′-2″ (305) Standard Curb 14″ HighCRRFCURB011A00 2′-0″ (610)S

Página 152

235ACCESSORY DIMENSIONS (cont)Horizontal Supply/Return Adapter Installation (581A155,180)NOTE: CRRFCURB013A00 is a fully factory preassembled horizont

Página 153

236ACCESSORY DIMENSIONS (cont)Factory-Installed Convenience OutletFactory-Installed Non-Fused Disconnecta48-4184a48-6126

Página 154

237ACCESSORY DIMENSIONS — 581A210-300a48-8234581A155, 180

Página 155

238SELECTION PROCEDUREI DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Gross CoolingCapacity (TC) . . . . . . . . . .

Página 156

239PERFORMANCE DATACOOLING CAPACITIES — STANDARD UNITS LEGENDNOTES:1. Direct interpolation is permissible. Do not extrap

Página 157

24PHYSICAL DATA — 580F036-073 LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-sentative for detai

Página 158

240PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is permissible.

Página 159

241581A155, 180PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is

Página 160

242PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is permissible.

Página 161

243PERFORMANCE DATA (cont)COOLING CAPACITIES — STANDARD UNITS (cont) LEGENDNOTES:1. Direct interpolation is permissible.

Página 162

244PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION LEGENDNOTES:1. Direct interpolation is permi

Página 163

245PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i

Página 164

246PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i

Página 165 - SOUND DATA

247PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i

Página 166

248PERFORMANCE DATA (cont)COOLING CAPACITIES, UNITS WITH HOT GAS REHEAT OPTION (cont) LEGENDNOTES:1. Direct interpolation i

Página 167

249PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGEND*Standard low-medium static drive range is 895 to 1147 rpm. Other rpms requi

Página 168

25PHYSICAL DATA — 580F036-073 (cont) LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-sentative fo

Página 169 - VERTICAL DISCHARGE DUCTING

250PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard low-medium static drive range is 895 to 1147 rpm. Other rpm

Página 170 - 581C 024-060 UNITS ARE

251581A155-300PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard low-medium static drive range is 873 to 1021 rpm

Página 171

252PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard low-medium static drive range is 873 to 1021 rpm. Alternate

Página 172

253PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 647-886 (208/230 and 460-v), 810-1

Página 173

254PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 647-886 (208/230 and 460-v), 810-1

Página 174

255PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 647-886 (208/230 and 460-v), 810-1

Página 175 - 579F180-300

256PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 949-1206High Range: 941-1176All ot

Página 176

257581A155-300PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 949-1206High Range: 941

Página 177

258PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 949-1206High Range: 941-1176All ot

Página 178

259PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High Range: 941-1176All ot

Página 179

26PHYSICAL DATA — 580F090,120,150 UNITS LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-sentati

Página 180

260PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High Range: 941-1176All ot

Página 181 - ACCESSORY DIMENSIONS (cont)

261PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High Range: 941-1176All ot

Página 182

262PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20

Página 183 - PERFORMANCE DATA — 579F

263PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20

Página 184 - COOLING CAPACITIES (cont)

264PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20

Página 185

265581A155-300PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 8

Página 186

266PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20

Página 187

267PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 896-1227 (20

Página 188

268PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High

Página 189

269PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High

Página 190

27PHYSICAL DATA — 580F090,120,150 UNITS (cont) LEGEND*Evaporator coil fin material/condenser coil fin material. Contact your local repre-s

Página 191

270PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive ranges:Low Range: 805-1007High

Página 192

271PERFORMANCE DATA (cont)ALTITUDE COMPENSATION* — 581A155,180(Natural Gas Units)*Includes a 4% input reduction per each 1,000 feet.†Orifices availabl

Página 193

272PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 581A155,180LEGEND *The static pressure must be added to external static pressure.

Página 194 - ALTITUDE DERATING FACTOR*

273PERFORMANCE DATA (cont)OUTDOOR SOUND POWER (TOTAL UNIT)LEGENDNOTE: Indoor sound power is available in Bryant’s Electronic Catalog Program (ECAT) fo

Página 195

274PERFORMANCE DATA (cont)EVAPORATOR FAN MOTOR SPECIFICATIONS — 581A210-300LEGENDACCESSORY/FIOP STATIC PRESSURE (in. wg) — 581A210-300LEGEND *The stat

Página 196 - EVAPORATOR-FAN MOTOR DATA

275ELECTRICAL DATA — 581A (cont)ELECTRICAL DATA — 581A155,180LEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance with NEC requirements for mult

Página 197

276ELECTRICAL DATA — 581A (cont)ELECTRICAL DATA — 581A210-300 WITHOUT CONVENIENCE OUTLETLEGEND*Fuse or HACR circuit breaker.NOTES:1. In compliance wit

Página 198 - (579F240, 208/230 V Shown)

277ELECTRICAL DATA — 581A (cont)ELECTRICAL DATA — 581A210-300 WITH OPTIONAL CONVENIENCE OUTLETLEGEND*Fuse or HACR circuit breaker.NOTES:1. In complian

Página 199

278TYPICAL WIRING SCHEMATICS — 581ALEGENDAHA — Adjustable Heat AnticipatorC—Contactor, CompressorCAP — CapacitorCB — Circuit BreakerCC — Cooling Compe

Página 200

279TYPICAL WIRING SCHEMATICS — 581A435286711011912PINKBLACKBLUENOTE 1NOTE 2RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMISER2 PLUGDIRECT

Página 201

28PHYSICAL DATA — 580F091,103,121,151 UNITSASHRAE 90.1 COMPLIANT UNITS LEGEND *Evaporator coil fin material/condenser coil fin material. C

Página 202 - (579F180 Shown)

280TYPICAL PIPING AND WIRING — 581A (581A155 Shown)LEGENDNEC — National Electrical Codeb48-1258

Página 203 - 580F180-300

281GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITSPACKAGED ROOFTOP ELECTRIC COOLING UNIT WITHGAS HEAT — CONSTANT VOLUME APPLICATION

Página 204 - (Weight Adders)

282GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)3. Burners shall be of the in-shot type constructed ofaluminum-coated stee

Página 205

283GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)2. Roof Curbs (Horizontal and Vertical):a. Formed of 16-gage galvanized st

Página 206

284GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)11. Low-Ambient Kits:When used, allows units to operate at lower outdooram

Página 207

285GUIDE SPECIFICATIONS — 581A210-300 UNITSPACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEAT — CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECIFICATIONS

Página 208 - 580F180-240

286GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)3. Optional pre-coated aluminum-fin coils shall have adurable epoxy-phenolic coating to provide prot

Página 209

287GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)M. Special Features:Certain features are not applicable when the featuresdesignated * are specified.

Página 210 - 1'-6 5/16"

288GUIDE SPECIFICATIONS — 581A210-300 UNITS (cont)11. Non-Fused Disconnect Switch:Switch shall be factory-installed, internally mounted,NEC and UL app

Página 211

289CONTROLSOPERATING SEQUENCE, SIZE 024-151 UNITSCooling, Units Without Economizer — When thermostat callsfor cooling, terminals G and Y1 are energize

Página 212

29PHYSICAL DATA — 580F091,103,121,151 UNITS (cont)ASHRAE 90.1 COMPLIANT UNITS (cont) LEGEND *Evaporator coil fin material/condenser coil f

Página 213 - PERFORMANCE DATA

290CONTROLS (cont)Heating, Units Without Economizer — When the thermostatcalls for heating, power is sent to W on the IGC (integrated gasunit controll

Página 214

291CONTROLS (cont)When the thermostat is satisfied and W1 and W2 are deener-gized, the IFM continues to run and the economizer damperthen moves to the

Página 215

292CONTROLS (cont)If field-installed accessory CO2 sensors are connected to theEconoMi$er IV control, a demand controlled ventilation strategywill beg

Página 216

293APPLICATION DATA1. CONDENSATE DRAIN PAN — A sloped condensate drainpan is supplied on all units. The condensate pan must beexternally trapped. Cond

Página 217

294APPLICATION DATA (cont)c. E-COATED ALUMINUM FIN coils undergo a preciselycontrolled scientific process that bonds an impermeableepoxy coating to th

Página 218

295APPLICATION DATA (cont)b. CONTROL FEATURES — The EconoMi$er IV controllerprovides superior functionality for rooftop unit operation.EconoMi$er IV c

Página 219

296APPLICATION DATA (cont)ECONOMI$ER IV SENSOR USAGE CHART*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As suc

Página 221

Copyright 2007 Bryant Heating & Cooling Systems Printed in U.S.A. 3/07 Catalog No. PDS580F-36-4SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT

Página 222

3FEATURES/BENEFITS (cont)EASY INSTALLATION AND CONVERSIONAll Units are Shipped in the Vertical Duct Configuration forfit-up to standard roof curbs. Th

Página 223

30BASE UNIT DIMENSIONS — 580F036-072a48-8195580F036-151

Página 224

31BASE UNIT DIMENSIONS — 580F073a48-8196580F036-151

Página 225

32BASE UNIT DIMENSIONS — 580F090,120,150a48-8197580F036-151

Página 226

33BASE UNIT DIMENSIONS — 580F091,103,121,151a48-8198580F036-151

Página 227

34ACCESSORY DIMENSIONS — 580FROOF CURBACCESSORYA UNIT SIZECRRFCURB001A011′-2″[356]580F036-073CRRFCURB002A012′-0″[610]NOTES:1. Roof curb accessory is s

Página 228 - PHYSICAL DATA — 581A155,180

35ACCESSORY DIMENSIONS — 580F (cont)CONNECTORPKG. ACCY.BCD ALT DRAIN HOLEGAS POWER CONTROLACCESSORY POWERCRBTMPWR001A012′-87/16″[827]1′-1015/16″[583]1

Página 229 - PHYSICAL DATA — 581A210-300

36SELECTION PROCEDURE (with 580F060 example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC). .

Página 230 - PHYSICAL DATA (cont)

37PERFORMANCE DATACOOLING CAPACITIESStandard Ratings LEGENDNOTES:1. Direct interpolation is permissi

Página 231

38PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)580F072 (6 TONS)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF1800/0.06 2100/0.0

Página 232

39PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)580F091 (71/2 TONS)Temp (F)Air EnteringCondenser(Edb)Air Entering Evaporator — Cfm/BF2250/0.10 2800/

Página 233 - 581A155, 180

4FEATURES/BENEFITS (cont)INDOOR-AIR QUALITY (IAQ) BEGINS WITH BRYANT ROOF-TOPS — Sloped condensate pans minimize biological growth inrooftop units in

Página 234 - 581A155,180

40PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)Standard Ratings LEGENDNOTES:1. Direct interpolation is permissible. Do not

Página 235

41PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS LEGEND See page 74 for general fan performance notes.

Página 236

42PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance note

Página 237

43PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance note

Página 238 - SELECTION PROCEDURE

44PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1300 to 1685 rpm. All ot

Página 239

45PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1070 to 1460 rpm. All oth

Página 240

46PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 590 to 840 rpm. All other

Página 241

47PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other

Página 242

48PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All other

Página 243

49PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other

Página 244

5MODEL NUMBER NOMENCLATURE580F036-151 3 to 121/2 TonsNOTE: The example model number 580FEV090180KV designates a 7 1/2 ton 460-3-60 volt gas/electric r

Página 245 - 581A155-300

50PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All other

Página 246

51PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other

Página 247

52PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 835 to 1085 rpm. All other

Página 248

53PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All other

Página 249

54PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All other

Página 250

55PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 835 to 1085 rpm. All other

Página 251

56PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All other

Página 252

57PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All other

Página 253

58PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All other

Página 254

59PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS LEGEND See page 74 for general fan performance notes.

Página 255

6MODEL NUMBER NOMENCLATURE581B036-150 (Standard) 3 to 121/2 TonsNOTE: The example model number 581BEV090180HQ designates a 7 1/2 ton 460-3-60 volt gas

Página 256

60PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance not

Página 257

61PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND See page 74 for general fan performance not

Página 258

62PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1300 to 1685 rpm. All o

Página 259

63PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 1070 to 1460 rpm. All o

Página 260

64PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 590 to 840 rpm. All othe

Página 261

65PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All othe

Página 262

66PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All oth

Página 263

67PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All othe

Página 264

68PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All oth

Página 265

69PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 685 to 935 rpm. All othe

Página 266

7MODEL NUMBER NOMENCLATURE581C024-060 (Standard Efficiency) — 2 to 5 TonsNOTE: The example model number 581CEV060150HQ designates a 5 ton 460-3-60 vol

Página 267

70PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 835 to 1085 rpm. All oth

Página 268

71PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All oth

Página 269

72PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 860 to 1080 rpm. All oth

Página 270

73PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont) LEGEND*Motor drive range: 830 to 1130 rpm. All oth

Página 271

74PERFORMANCE DATA (cont)GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES1. Values include losses for filters, unit casing, and wet coils. See thispage f

Página 272

75PERFORMANCE DATA (cont)FAN RPM AT MOTOR PULLEY SETTINGS* — 580F036-073*Approximate fan rpm shown.†Indicates alternate motor and drive package.**Indi

Página 273

76PERFORMANCE DATA (cont)POWER EXHAUST OPTIONS VERTICAL — MOUNTED IN ECONOMIZER HOODPOWER EXHAUSTPART NO.POWER EXHAUST DESCRIPTIONAPPLICATION USAGEPOW

Página 274

77PERFORMANCE DATA (cont)OPTIONAL POWER EXHAUSTPOWER REQUIREMENTSLEGENDEVAPORATOR-FAN MOTOR EFFICIENCY*Single phase/three-phase.NOTE: The EPACT (Ener

Página 275 - ELECTRICAL DATA — 581A (cont)

78PERFORMANCE DATA (cont)EVAPORATOR-FAN MOTOR PERFORMANCELEGENDBHP — Brake Horsepower*Extensive motor and electrical testing on these units ensures th

Página 276

79ELECTRICAL DATA LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In compliance

Página 277

8MODEL NUMBER NOMENCLATURE — 579F180-300MODEL NUMBER NOMENCLATURE580F180-300NOTES:1. All indoor-fan motors 5 hp and larger meet the minimum efficiency

Página 278 - 581A155, 460-3-60 Shown

80ELECTRICAL DATA (cont)UNIT SIZE580FNOMINALV-PH-HzIFM TYPECONV OUTLETVOLTAGE RANGECOMPRESSOR (each) OFM (each) IFM FLACOMBUSTIONFAN MOTORPOWER SUPP

Página 279

81ELECTRICAL DATA (cont) LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In com

Página 280

82ELECTRICAL DATA (cont) LEGEND*Used to determine minimum disconnect per NEC.†Fuse or HACR circuit breaker.NOTES:1. In com

Página 281

83TYPICAL WIRING SCHEMATICS — 580F036-151(580F090, 460-3-60 Shown)CIRCUITBREAKERVOLTS MFG. PT. NO.MUST TRIPAMPSCB 24 VPOTTER & BRUMFIELD3.2W2BX-10

Página 282

84TYPICAL WIRING SCHEMATICS — 580F036-151 (cont)LEGENDIAQ — Indoor Air QualityLA — Low Ambient Lockout DevicePOT — PotentiometerOAT — Outdoor-Air Temp

Página 283

85TYPICAL WIRING SCHEMATICS — 580F (cont)C2 FOR 008-014 UNITSLINE SIDEC1113232321BLUBLUGRAGRAREDGRAREDREDYELYEL208-230-1 ONLY240VH1H1H3H2H2H4TRAN4TRA

Página 284

86TYPICAL PIPING AND WIRING — 580F036-151NO.2NO.1CONVENIENCEOUTLETVertical Discharge DuctingHorizontal Discharge DuctingNEC — National Electrical Code

Página 285

87PHYSICAL DATA — 581B036-072 LEGEND*Single phase/three phase.†Indicates automatic reset.**60,000 and 72,000 Btuh heat input units have 2

Página 286

88PHYSICAL DATA — 581B036-072 (cont) LEGEND*Single phase/three phase.†Indicates automatic reset.**60,000 and 72,000 Btuh heat input units

Página 287

89PHYSICAL DATA — 581B090-150 LEGEND*Single phase/three phase.†Indicates automatic reset.**72,000 Btuh heat input units have 2 burners.11

Página 288

9MODEL NUMBER NOMENCLATURE581A155, 180, 181 — 13 to 15 TonsMODEL NUMBER NOMENCLATURE581A210-300 — 18 to 25 Tons*See pages 212 and 213 for cooling capa

Página 289 - CONTROLS

90PHYSICAL DATA — 581B090-150 (cont) LEGEND*Single phase/three phase.†Indicates automatic reset.**180,000 Btuh heat input units have 2 bu

Página 290 - CONTROLS (cont)

91BASE UNIT DIMENSIONS — 581B036-072a48-8199581B036-150

Página 291

92BASE UNIT DIMENSIONS — 581B090-150UNIT581BSTD UNIT WEIGHTECONOMI$ER IVWEIGHTVERT. ECON IVW/P.E. WEIGHT(A)CORNER WEIGHT(B)CORNER WEIGHT(C)CORNER WEIG

Página 292

93ACCESSORY DIMENSIONS — 581B036-072a48-8201581B036-150

Página 293 - APPLICATION DATA

94ACCESSORY DIMENSIONS — 581B090-150a48-8202581B036-150

Página 294 - APPLICATION DATA (cont)

95SELECTION PROCEDURE (With 581B048 Example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC) .

Página 295

96PERFORMANCE DATACOOLING CAPACITIES, STANDARD UNITSStandard RatingsLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The foll

Página 296

97PERFORMANCE DATA (cont)COOLING CAPACITIES, STANDARD UNITS (cont)Standard RatingsLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapola

Página 297

98PERFORMANCE DATA (cont)COOLING CAPACITIES, STANDARD UNITS (cont)Standard RatingsLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapola

Página 298

99PERFORMANCE DATA (cont)COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTIONLEGENDNOTES:1. Direct interpolation