Residential H&V - 60Hz R22 & R410A - Geothermal Heat Pumps - Rev.: 21 Aug, 2007D
51
UNIT STARTING AND OPERATING CONDITIONS
Operating Limits
Environment – Units are designed for indoor installation
only. Never install units in areas subject to freezing or where
humidity levels could cause cabinet condensation (such as
unconditioned spaces subject to 100% outside air).
Power Supply – A voltage variation of +/– 10% of
nameplate utilization voltage is acceptable.
Starting Conditions
Consult Table 8 for the particular model. Starting
conditions vary depending upon model and are based
upon the following notes:
Notes:
1. Conditions in Table 8 are not normal or continuous
operating conditions. Minimum/maximum limits are
start-up conditions to bring the building space up to
occupancy temperatures. Units are not designed to
operate under these conditions on a regular basis.
2. Voltage utilization range complies with ARI
Standard 110.
Determination of operating limits is dependent primarily
upon three factors: 1) return air temperature. 2) water
temperature, and 3) ambient temperature. When any
one of these factors is at minimum or maximum levels,
the other two factors should be at normal levels to insure
proper unit operation.
Extreme variations in temperature and humidity
and/or corrosive water or air will adversely affect unit
performance, reliability, and service life.
Table 8: Operating Limits
Operating Limits
GT-PX/GT-PG GT-G
Cooling Heating Cooling Heating
Air Limits
Min. ambient air, DB 45°F [7°C] 39°F [4°C] 45°F [7°C] 39°F [4°C]
Rated ambient air, DB 80.6°F [27°C] 68°F [20°C] 80.6°F [27°C] 68°F [20°C]
Max. ambient air, DB 110°F [43°C] 85°F [29°C] 110°F [43°C] 85°F [29°C]
Min. entering air, DB/WB 50°F [10°C] 40°F [4.5°C] 50°F [10°C] 50°F [10°C]
Rated entering air, DB/WB 80.6/66.2°F [27/19°C] 68°F [20°C] 80.6/66.2°F [27/19°C] 68°F [20°C]
Max. entering air, DB/WB 110/83°F [43/28°C] 80°F [27°C] 110/83°F [43/28°C] 80°F [27°C]
Water Limits
Min. entering water 30°F [-1°C] 20°F [-6.7°C] 30°F [-1°C] 20°F [-6.7°C]
Normal entering water 50-110°F [10-43°C] 30-70°F [-1 to 21°C] 50-110°F [10-43°C] 30-70°F [-1 to 21°C]
Max. entering water 120°F [49°C] 90°F [32°C] 120°F [49°C] 90°F [32°C]
Normal water ow
1.5 to 3.0 gpm/ton 1.5 to 3.0 gpm/ton
2.0 to 3.9 l/m per kW 2.0 to 3.9 l/m per kW