IMPORTANT — READ BEFORE INSTALLING1. Read and become familiar with these installation in-structions before installing this unit.2. Be sure the install
C. DefrostDefrost board (DB) is a time and temperature control, whichincludes a field-selectable time period between checks for frost(30, 50, and 90 mi
SERVICECAUTION:When servicing unit, shut off all electri-cal power to unit to avoid shock hazard or injury fromrotating parts.I. CLEANINGInspect unit
II. LUBRICATIONA. CompressorsCompressor has its own oil supply. Loss of oil due to a leak inthe system should be the only reason for adding oil after
TROUBLESHOOTING CHART, HEATING CYCLELEGENDN.C. — Normally Closed—13—
TROUBLESHOOTING CHART, COOLING CYCLELEGENDTXV — Thermostatic Expansion ValveCopyright 1995 Carrier Corporation CATALOG NO. BDP-3357-502
START-UP CHECKLISTI. PRELIMINARY INFORMATIONOUTDOOR: MODEL NO.INDOOR: MODEL NO.SERIAL NO.SERIAL NO.ADDITIONAL ACCESSORIESB. Pre-Start-UpOUTDOOR UNITIS
C. Start-UpCHECK INDOOR-FAN SPEED AND RECORD.CHECK OUTDOOR-FAN SPEED AND RECORD.AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREME
UNIT575AUNIT W/ALUMINUM-FINCOILUNIT W/COPPER-FINCOILWEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL)Std Unit Corner W Corner X Corner Y C
Table 1 — Physical DataUNIT 575A 090OPERATING WEIGHT (lb)Aluminum Coils (Standard) 540Copper Coils (Optional) 608RIGGING WEIGHT (lb)Aluminum Coils (St
III. COMPLETE REFRIGERANT PIPING CONNECTIONSSuction connection is sweat with plastic cap; liquid connec-tion is sweat with plastic cap. Refer to Table
LEGENDNEC — National Electrical CodeTXV — Thermostatic Expansion Valve*Accessory item.†Field supplied.NOTES:1. All piping must follow standard refrige
IV. MAKE ELECTRICAL CONNECTIONSWARNING:Unit cabinet must have an uninterrupted,unbroken electrical ground to minimize the possibilityof personal injur
Table 4 — Electrical DataUNIT575ANOMINAL VOLTAGE(V-Ph-Hz)VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MINIMUM DISCONNECTMin Max RLA LRA FLA MCAMAX FUSE O
C. Field Control WiringInstall an approved accessory thermostat assembly accord-ing to installation instructions included with the accessory.Locate th
B. Oil ChargingAllow unit to run for about 20 minutes. Stop unit and checkcompressor oil level. Add oil only if necessary to bring oil intoview in sig