
SSP-SVX15C-EN
29
Condition
Resulting Operations
If the disconnect switch is in the
ON position…
1. Current is supplied to the compressor crankcase heater(s) (CCH) through the normally closed contacts
of the crankcase heater relay (CHR) when the compressor is not running.
2. The phase monitor (PM) is powered.
3. The phase monitor (PM) looks at the incoming power to verify that there is no reversed phase, no
phase imbalance, and no loss of phase. If the phase monitor detects any of these three conditions, it
will shut off control voltage.
4. The control transformer (TNS) is powered.
5. The ReliaTel ™ control board (RTRM) is powered and performs self-diagnostic checks to insure that all
internal controls are functioning.
6. The ReliaTel ™ control board (RTRM) checks the configuration parameters against the components
connected to the system.
7. The system LED located on the RTRM module is turned ON within one second after power-up if all
internal operations are correct.
8. The communications board (COMM) is powered if installed.
9. The indoor thermostat (TS) is powered.
Mechanical Heat
In Heat mode the switchover valve (SOV) is turned OOFFFF.
When a request for heating occurs, the control system
turns OONN the mechanical heat (compressors) to
perform heating. Dual circuit heat pumps are factory
configured to have 2-step mechanical heating enabled
(RTRM J4-3 tied to ground).
The staging sequence depends on the type of
mechanical heating that is enabled.
• If 1-Step mechanical heating is enabled (RTRM J4-3
not tied to ground), the unit will stage according to
Table 9, p. 31, as a result of the proportional/
integral control algorithms.
• Units with 2-step mechanical heating will stage
according to Table 10, p. 31, as a result of the
proportional/integral control algorithms.
With mechanical heating, when a heat request is turned
OONN, the Indoor Fan request is turned OONN. When the
heat request is turned OOFFFF, the Indoor Fan request is
turned OOFFFF after a specified delay (60 seconds on all
dual-compressor units and 80 seconds on all single
compressor units). See Table 7, p. 30, Table 8, p. 31,
Table 9, p. 31, and Table 10, p. 31 in this document for
the staging, sequence, and control.
Auxiliary Heat
Auxiliary Heat is factory disabled on all Odyssey units
(Jumper placed between J2-1 and J2-2 RTRM inputs). If
configured (Jumper wire cut or removed between J2-1
and J2-2 on RTRM) and installed, Auxiliary Heat is
enabled or disabled by Smart Recovery.
Smart Recovery
Smart Recovery dictates that if the Active Zone
Temperature is making a recovery using only
mechanical heating toward the setpoint at a rate of at
least 6°F/hour (0.1°F/minute), the electric heat is
disabled. If Smart Recovery is not disabling electric
heat, an approximate 9 minute stage-up delay (plus or
minus a few minutes) is provided for each stage to
allow time for recovery to begin. Stages of electric heat
are enabled and energized as necessary to meet
heating demand. When the request for Auxiliary Heat is
removed, the Indoor Fan request is turned OOFFFF at the
same time as the Electric Heat Stages. See Table 7, p.
30, Table 8, p. 31, Table 9, p. 31, and Table 10, p. 31 for
the staging, sequence, and control.
All split system units are also configured from the
factory for only 1-Stage of Electric Heat (Jumper placed
between J1-3 and J1-6 RTRM inputs). To enable two
stages of Electric Heat, cut or remove the jumper
between J1-3 and J1-6 RTRM inputs.
Emergency Heat
When Emergency Heat mode is requested and
Auxiliary Electric Heat is configured and installed, only
the Auxiliary Electric Heat will be turned OONN to satisfy
the Heat request. Mechanical heat will be held OOFFFF.
When the request for Emergency Heat is initiated, the
Indoor Fan request is turned OONN 1 second before the
electric heat stages are activated. See Table 7, p. 30,
Table 8, p. 31, Table 9, p. 31, and Table 10, p. 31for the
staging, sequence, and control.
Cooling
With a request for Cooling, the RTRM stages the
circuits and control normally for single and dual stage
SSttaarrtt--UUpp
Comentários a estes Manuais