Installation Instructions
286B / 289B
EVOLUTIONt SERIES 2--STAGE HEAT PUMP
WITH PURON
R
REFRIGERANT
2TO5TONS
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety--alert symbol
!
!
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position and
install a lockout tag. There may be more than 1 disconnect
switch. Lock out and tag switch with a suitable warning label.
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
!
WARNING
Indoor Thermostat Control Options
Model
Evolution
Control
Standard
2 --- s t a g e
Thermostat
286B / 289B Yes Yes
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon--based caulk. (See Fig.
1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
When outdoor unit is connected to factory--approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field--supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid--line size is 3/8--in. OD for all
residential applications including long line applications.
IMPORTANT: Always install the factory--supplied liquid--line
filter drier. Obtain replacement filter driers from your distributor or
branch.
Vista de página 0
1 2 3 4 5 6 ... 15 16

Resumo do Conteúdo

Página 1 - Installation Instructions

Installation Instructions286B / 289BEVOLUTIONt SERIES 2--STAGE HEAT PUMPWITH PURONRREFRIGERANT2TO5TONSSAFETY CONSIDERATIONSImproper installation, adju

Página 2 - INSTALLATION

10MAJOR COMPONENTS2--Stage Control BoardThe HP control board controls the following functions:S High and low stage compressor contactor operationS Out

Página 3 - Make Piping Connections

11After the brownout defeat is set, power down and reinstall theOAT/OCT sensor and remove the short from the forced defrostpins. As long as the short

Página 4

12The thermistor comparison is not performed during low ambientcooling or defrost operation.Failed Thermistor Default OperationFactory defaults have b

Página 5

13Table 6 – TROUBLESHOOTINGOPERATIONFAULTAMBER LEDFLASHCODEPOSSIBLE CAUSE AND ACTIONStandby – no call for unit operation NoneOn solid, noflashNormal o

Página 6

14OORVS Cooling O/B W2 W1 W1Heat Stage 3 W/W1 W2Heat/Cool Stage 1 Y1 / W2 Y1 Y1Heat/Cool Stage 2 Y/Y2 Y/Y2 Y2Fan G G24VAC Hot Heating Rh R24VAC Hot Co

Página 7 - 289B036 9.06 10.23 11.90

15FINAL CHECKSIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring is routed away from tubing and sheetmetal edges to

Página 8 - GENERAL INFORMATION

16Manufacturer reserves the right to dis continue, or change at any time, specifications or designs without notice and without incurring obligations.E

Página 9 - Check Charge

2INSULATIONSUCTION TUBELIQUID TUBEOUTDOOR WALL INDOOR WALLLIQUID TUBESUCTION TUBEINSULATIONCAULKHANGER STRAP(AROUND SUCTIONTUBE ONLY)JOIST1” (25.4 mm)

Página 10

3In Long--Line Applications, Install Liquid--LineSolenoid Valve (LSV)For refrigerant piping arrangements with equivalent lengths greaterthan 80 ft. (2

Página 11 - THERMISTOR CURVE

4Install Liquid--Line Filter Drier Indoor!WARNINGUNIT OPERATION AND SAFETY HAZARDFailure to follow this warning could result in personal injuryor equi

Página 12 - 286B / 289B

5Make Electrical Connections!WARNINGELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury or death.Do not supply power

Página 13

6Airflow Selection for Variable Speed Furnaces(non--communicating)The variable speed furnaces provide blower operation to match thecapacities of the c

Página 14

7Communication and Status Function LightsFor Evolution Control only, Green communications (COMM)LightA green LED (COMM light) on the outdoor board (se

Página 15

8UTILITY RELAY *UTILITY SIGNALOPEN RELAY* SUPPLIED BY UTILITY PROVIDERA B CA B CA12260LLSLiquid Line SolenoidA B CA B CA12261Fig. 6 -- 2-

Página 16

9Status code 4 shows the fan delay defeat is active (no delay).Status code 3 shows that it is not active (20 second delay).The code will continue to b