Form No. PDS 548F.36.4
COMMERCIAL
SINGLE PACKAGE ROOFTOP
STANDARD AND HIGH EFFICIENCY
HEAT PUMP UNITS
Standard-efficiency (548F), and high-efficiency (542J and
549B) heat pump units with:
Pre-painted galvanized steel cabinet for long life and quality
appearance
Commercial strength base rails with built-in rigging capability
Convertible design for vertical or horizontal supply/return
Non-corrosive, sloped condensate drain pan, meets
ASHRAE 62 (IAQ)
Two-inch return-air filters
A wide assortment of factory-installed options available,
including high static drives that provide additional perfor-
mance range
Optional gear driven EconoMi$er with CO
2
ventilation control
(2 to 10 vac actuator)
Optional gear-driven EconoMi$er with 4 to 20 mA actuator for
EMS controls
State-of-the-art defrost system
Dependable 4-way valve operation
Heat Options
Field-installed electric heat available
Glycol hydronic coils
FEATURES/BENEFITS
Every compact one-piece unit arrives fully assembled,
charged, tested, and ready to run.
QUIET, EFFICIENT OPERATION AND DEPENDABLE PER-
FORMANCE —
Compressors have vibration isolators for quiet
operation. Efficient fan and motor design permits operation at
low sound levels.
Unit sizes 090-180 offer lower utility costs through part-load
operation using 2 stages of cooling.
Quiet and efficient operation is provided by belt-driven indoor
fans (standard on all units over 5 tons). The belt-driven indoor
fan is equipped with variable-pitch pulleys which allow adjust-
ment within the rpm ranges of the factory-supplied pulleys.
Increased operating efficiency is achieved through computer-
designed coils featuring staggered internally enhanced copper
tubes. Fins are ripple-edged for strength, lanced, and double
waved for higher heat transfer.
Models 542J, 548F, 549B
Sizes 036-180
DuraPac and DuraPac Plus
3 to 15 Tons
548F036-072
549B036-072
548F090-120
549B090-120
542J150,180
Vista de página 0
1 2 3 4 5 6 ... 121 122

Resumo do Conteúdo

Página 1 - Models 542J, 548F, 549B

Form No. PDS 548F.36.4COMMERCIALSINGLE PACKAGE ROOFTOPSTANDARD AND HIGH EFFICIENCYHEAT PUMP UNITSStandard-efficiency (548F), and high-efficiency (542J

Página 2 - TABLE OF CONTENTS

10CONTROLSOPERATING SEQUENCE — 548F036-120 AND 549B036-120Cooling, Units Without Economizer — When thermostat callsfor cooling, terminals G and Y1 are

Página 3

100GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)15. Compressor Cycle Delay:Unit shall be prevented from restarting for minimumof 5 min. aft

Página 4 - OPTIONS AND ACCESSORIES

101MODEL NUMBER NOMENCLATURE — 542J150,180 UNITSNominal Cooling Capacity150 – 12 Tons180 – 15 TonsFactory-Installed OutdoorAir Upgrade OptionsC – Econ

Página 5 - (150,180 shown)

102ARI* CAPACITY RATINGS542J150,180 UNITS LEGEND*Air-Conditioning and Refrigeration Institute.NOTES:542J units are rated in ac

Página 6 - AD-DME1711-1

103PHYSICAL DATA (cont)542J150,180 LEGEND*Weight of 14 in. roof curbUNIT 542J 150 180OPERATING WT (lb)Unit1615 1925Electric Heat65 65EconoMi$er

Página 7 - GLYCOL COIL (150,180 only)

104BASE UNIT DIMENSIONS*Units with aluminum indoor and outdoor coil fins.UNIT542JMAXIMUM SHIPPING WEIGHT*Lb Kg1501895 8601802205 1000 LEGENDUNIT5

Página 8

105ACCESSORY DIMENSIONSPKG NO. REF.CURBHEIGHTDESCRIPTIONCRRFCURB010A001′-2″(305)Standard Curb14″ HighCRRFCURB011A002′-0″(610)Standard Curb forUnits Re

Página 9

106ACCESSORY DIMENSIONS (cont)Horizontal Adapter Installation — 542J150,180NOTE: CRRFCURB013A00 is a fully factory pre-assembled horizontaladapter whi

Página 10 - CONTROLS

107ACCESSORY DIMENSIONS (cont)2'-1 5/8"2'-2 1/16"1'-6 5/16"Non-Fused Disconnect — 542J150,180Power Exhaust — 542J150,180

Página 11 - CONTROLS (cont)

108SELECTION PROCEDURE (WITH 542J180 EXAMPLE)I DETERMINE HEATING AND COOLING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC).

Página 12

109PERFORMANCE DATACOOLING CAPACITIESLEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may be used:tlwb

Página 13

11CONTROLS (cont)NOTE: Compressor no. 2 cannot be energized unless there is asignal for Y2 from the space thermostat.4. If compressor no. 2 is energiz

Página 14 - APPLICATION DATA

110PERFORMANCE DATA (cont)INTEGRATED HEATING CAPACITIES LEGEND NOTES:1. Integrated heating capacity ratings shown are not adjuste

Página 15 - APPLICATION DATA (cont)

111PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS LEGENDRefer to this page for general Fan Performance notes.

Página 16 - TYPICAL PIPING AND WIRING

112PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 542J150,180 LEGEND*Units with electric heat are not designed t

Página 17

113PERFORMANCE DATA (cont)ELECTRIC HEATING CAPACITIES — 542J150,180*Maximum number of stages using accessory outdoor-air thermostats. NOTE: Heaters ar

Página 18 - 548F072-120

114PERFORMANCE DATA (cont)INDOOR-FAN MOTOR PERFORMANCE — 542J150,180 LEGEND*Extensive motor and electrical testing on these units ensure

Página 19 - 548F036-120

115TYPICAL WIRING SCHEMATIC542J180, 460-3-60 Shown50TFQ004-012542J150,180

Página 20

116TYPICAL WIRING SCHEMATIC (cont)LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATICAHA —Adjustable Heat AnticipatorBKR W/AT —Breaks with Amp TurnsC —Conta

Página 21

117TYPICAL WIRING SCHEMATIC (cont)5L3 3L2 1L1 LINE6T3 4T2 2T1 LOADOptional Non-Fused Disconnect — 542J150,180NOTES:1. If the non-fused disconne

Página 22 - BASE UNIT DIMENSIONS (cont)

118GUIDE SPECIFICATIONS — 542J150,180 UNITSPACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP — CON-STANT VOLUME APPLICATIONHVAC GUIDE SPECIFICATIONSSIZE RANGE: 12

Página 23

119GUIDE SPECIFICATIONS — 542J150,180 UNITS (cont)b. E-Coated aluminum-fin coils shall have a flexibleepoxy polymer coating uniformly applied to all

Página 24

12CONTROLS (cont)Heating, Units Without Economizer — With unit main poweron, set thermostat at HEAT position and desired room tempera-ture. Set fan sw

Página 25

120GUIDE SPECIFICATIONS — 542J150,180 UNITS (cont)K. Electrical Requirements:All unit power wiring shall enter unit cabinet at a singlefactory-predril

Página 26

121GUIDE SPECIFICATIONS — 542J150,180 UNITS (cont)15. Power Exhaust Accessory:Power exhaust shall be used to provide systemexhaust of up to 100% of re

Página 27

Copyright 2002 Bryant Heating & Cooling Systems Printed in U.S.A. 1/02 Catalog No. 5254-804SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT MUS

Página 28

13CONTROLS (cont)OPERATING MODESBP —Building Pressurization: Indoor fan on, economizer energized to fully open position, power exhaust disabled.E—Evac

Página 29

14CONTROLS (cont)LEGENDAPPLICATION DATA1. OUTDOOR INSTALLATION — Units approved for outdoorinstallation only.2. DUCTWORK — Secure vertical discharge d

Página 30

15APPLICATION DATA (cont)Concentric Duct Distribution —542J150,180NOTE:1. Do not drill in this area, damage to basepan may result inwater leak.2. A 90

Página 31

16TYPICAL PIPING AND WIRINGVertical Discharge Ducting — 548F036-120 and 549B036-120Horizontal Discharge Ducting — 548F036-120 and 549B036-120LEGENDNEC

Página 32

17TYPICAL PIPING AND WIRING (cont)LEGENDNOTES:1. Illustration shown is a general guide only and is not intended for or to include all details for any

Página 33

18MODEL NUMBER NOMENCLATURE — 548F UNITS(ODS Model Number)ARI* CAPACITY RATINGS548F036-060548F072-120LEGEND*Air Conditioning and Refrigeration Institu

Página 34

19PHYSICAL DATA548F036-072LEGEND*Weight of 14-in. roof curb.†Single phase/three phase.NOTE: The 548F units have a loss-of-charge switch located in the

Página 35

2TABLE OF CONTENTSPageFeatures/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Options and Accessories . . . . . . . .

Página 36

20PHYSICAL DATA (cont)548F090-120 LEGEND*Weight of 14-in. roof curb.NOTE: The 548F units have a loss-of-charge switch located in the liqu

Página 37

21BASE UNIT DIMENSIONS548F036-07250TFQ004-012548F036-120

Página 38

22BASE UNIT DIMENSIONS (cont)548F090-12050TFQ004-012548F036-120

Página 39

23ACCESSORY DIMENSIONSTO ENSURE AIRTIGHT CONNECTION.PLACE UNIT AS CLOSE TO THISEND AS POSSIBLETO ENSURE AIRTIGHT CONNECTION.PLACE UNIT AS CLOSE TO THI

Página 40

24ACCESSORY DIMENSIONS (cont)TO ENSURE AN AIRTIGHT CONNECTION,PLACE UNIT ON CURB AS CLOSE TODUCT END AS POSSIBLE.TO ENSURE AN AIRTIGHT CONNECTION,PLAC

Página 41

25SELECTION PROCEDURE (WITH 548F048 EXAMPLE)I DETERMINE COOLING AND HEATING LOADS ATDESIGN CONDITIONS.Given:Required Cooling Capacity (TC) . . . . . .

Página 42

26PERFORMANCE DATACOOLING CAPACITIES548F036 (3 TONS)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/BF900/0.10 1200/0.15 1500/0.21Indoor Ent

Página 43

27PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)548F072 (6 TONS)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/BF1800/0.10 2400/0.13 3000

Página 44

28PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)LEGENDNOTES:1. Direct interpolation is permissible. Do not extrapolate.2. The following formulas may

Página 45

29PERFORMANCE DATA (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. indicate

Página 46

3INTEGRATED ECONOMI$ERS AND OUTDOOR AIROptional EconoMi$ers and manual outdoor-air dampers intro-duce outdoor air which mixes with the conditioned air

Página 47

30PERFORMANCE DATA (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. indicates

Página 48

31PERFORMANCE DATA (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. indicates

Página 49

32PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGENDRefer to page 51 for general Fan Performance notes.LEGEND*Motor drive range:

Página 50

33PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGENDRefer to page 51 for general Fan Performance notes.LEGEND*Motor drive

Página 51

34PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGENDRefer to page 51 for general Fan Performance notes.LEGEND*Motor drive

Página 52

35PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-sup

Página 53

36PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-sup

Página 54

37PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard motor drive range: 590 to 840 rpm. Alternate motor driverang

Página 55

38PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms require field-supp

Página 56

39PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 685 to 935 rpm. All other rpms require field-suppl

Página 57 - ELECTRICAL DATA (cont)

4OPTIONS AND ACCESSORIES*Factory-installed.†Field-installed.**Special order/DEC only.NOTES: 1. Refer to unit price pages or contact your local represe

Página 58

40PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms require field-supp

Página 59

41PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGEND*Standard motor drive range: 685 to 935 rpm. Alternate motor driverang

Página 60

42PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGENDRefer to page 51 for general Fan Performance notes.LEGEND*Motor drive range

Página 61

43PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGENDRefer to page 51 for general Fan Performance notes.LEGEND*Motor driv

Página 62

44PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGENDRefer to page 51 for general Fan Performance notes.LEGEND*Motor driv

Página 63

45PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-s

Página 64

46PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 1300 to 1685 rpm. All other rpms require field-s

Página 65

47PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 590 to 840 rpm. Alternate motor drive range: 685

Página 66

48PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms require field-su

Página 67 - 549B072-120

49PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 685 to 935 rpm. All other rpms require field-sup

Página 68 - 549B036-120

5OPTIONS AND ACCESSORIES (cont)LOW AMBIENT CONTROLSStandard units are designed to operate in cooling at outdoor temperatures down to 25 F (for size 03

Página 69

50PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Motor drive range: 860 to 1080 rpm. All other rpms require field-su

Página 70

51PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGEND*Standard motor drive range: 685 to 935 rpm. Alternate motor drivera

Página 71

52PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 548F036-072LEGENDFIOP — Factory-Installed Option*The static pressure must be added

Página 72

53PERFORMANCE DATA (cont)FLOW (cfm)00.10.20.30.40.5STATIC PRESSURE (in. wg)2 FANSOPERATING1 FANOPERATING2500200015001000500050004000300020001000000.10

Página 73

54PERFORMANCE DATA (cont)ELECTRIC HEATING CAPACITIES*Two heater packages required to provide kW indicated.†On units with factory-installed outlet, use

Página 74

55PERFORMANCE DATA (cont)INDOOR-FAN MOTOR PERFORMANCE — 548F UNITSLEGENDBHP — Brake Horsepower*Extensive motor and electrical testing on these units e

Página 75

56ELECTRICAL DATAUNITS WITHOUT ELECTRICAL CONVENIENCE OUTLETNOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-P H-HzIFMTYPEVO

Página 76

57ELECTRICAL DATA (cont)UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)NOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-P

Página 77

58ELECTRICAL DATA (cont)UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)NOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-P

Página 78

59ELECTRICAL DATA (cont)UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)NOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-P

Página 79

6OPTIONS AND ACCESSORIES (cont)CONTROLLERBAROMETRICRELIEF DAMPERSOUTDOOR AIRTEMPERATURESENSORGEAR-DRIVENDAMPERACTUATORECONOMI$ERPLUG204060801000ABCDOF

Página 80

60ELECTRICAL DATA (cont)UNITS WITH ELECTRICAL CONVENIENCE OUTLETNOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-PH-HzIFMTYP

Página 81

61ELECTRICAL DATA (cont)UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)NOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-P H-

Página 82

62ELECTRICAL DATA (cont)UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)NOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-PH-H

Página 83

63ELECTRICAL DATA (cont)UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)NOTE: Legend and Notes for Electrical Data are on page 64.UNIT548FNOMINALV-PH -

Página 84

64ELECTRICAL DATA (cont)LEGEND AND NOTES FOR ELECTRICAL TABLESLEGEND*Heaters are field installed only.†Used to determine minimum disconnect size per N

Página 85

65TYPICAL WIRING SCHEMATICLEGENDAHA —Adjustable Heat AnticipatorAWG —American Wire GageC —Contactor, CompressorCAP —CapacitorCB —Circuit BreakerCC —Co

Página 86

66TYPICAL WIRING SCHEMATIC (cont)12-PINFEMALE111210956784321MOLEXCONNECTORPL6121110987654321REDBLUBLKBRNGRYVIOPNKYELORNFIELD INSTALLEDOPTIONRATOATVIOW

Página 87

67MODEL NUMBER NOMENCLATURE(ODS Model Number)ARI* CAPACITY RATINGS549B036-060549B072-120LEGEND*Air Conditioning and Refrigeration Institute.†Applies o

Página 88

68PHYSICAL DATA549B036-072 LEGENDBASE UNIT 549B 036 048 060 072NOMINAL CAPACITY (tons)34 5 6OPERATING WEIGHT (lb)Unit500 550 590 630Durab

Página 89

69PHYSICAL DATA (cont)549B090,120 LEGENDBASE UNIT 549B 090 120NOMINAL CAPACITY (tons)71/210OPERATING WEIGHT (lb)Unit870 1000Durablade Eco

Página 90

7OPTIONS AND ACCESSORIES (cont)Factory-installed, internally mounted, NEC (National ElectricalCode) and UL (Underwriters’ Laboratories) approved non-f

Página 91

70BASE UNIT DIMENSIONS549B036-07250TFQ004-012549B036-120

Página 92

71BASE UNIT DIMENSIONS (cont)549B090,12050TFQ004-012549B036-120

Página 93

72ACCESSORY DIMENSIONSTO ENSURE AIRTIGHT CONNECTION.PLACE UNIT AS CLOSE TO THISEND AS POSSIBLETO ENSURE AIRTIGHT CONNECTION.PLACE UNIT AS CLOSE TO THI

Página 94

73ACCESSORY DIMENSIONS (cont)TO ENSURE AN AIRTIGHT CONNECTION,PLACE UNIT ON CURB AS CLOSE TODUCT END AS POSSIBLE.TO ENSURE AN AIRTIGHT CONNECTION,PLAC

Página 95

74SELECTION PROCEDURE (WITH 549B048 EXAMPLE)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS.Given:Required Cooling Capacity (TC). .

Página 96

75PERFORMANCE DATACOOLING CAPACITIES549B036 (3 Tons)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/Bf900/0.13 1200/0.17 1500/0.19Indoor Ent

Página 97

76PERFORMANCE DATA (cont)COOLING CAPACITIES (cont)549B072 (6 Tons)Temp (F)OutdoorEntering Air(Edb)Indoor Entering Air — Cfm/Bf1800/0.06 2100/0.066 240

Página 98

77PERFORMANCE DATA (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS LEGEND NOTES:1. indicates integ

Página 99

78PERFORMANCE DATA (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. indicate

Página 100 - 548F/549B036-120

79PERFORMANCE DATA (cont)INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont) LEGEND NOTES:1. indicate

Página 101 - 542J150,180

8OPTIONS AND ACCESSORIES (cont)Outdoor coil hail guard accessory (field installed) protects coilsagainst damage from hail and other flying debris.Coil

Página 102 - PHYSICAL DATA

80PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITSLEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface indicates

Página 103 - PHYSICAL DATA (cont)

81PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface in

Página 104 - BASE UNIT DIMENSIONS

82PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface in

Página 105 - ACCESSORY DIMENSIONS

83PERFORMANCE DATA (cont)FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)LEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface in

Página 106 - ACCESSORY DIMENSIONS (cont)

84PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITSLEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface indicat

Página 107

85PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface

Página 108

86PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGENDRefer to page 87 for general Fan Performance notes.NOTES:1.Boldface

Página 109 - PERFORMANCE DATA

87PERFORMANCE DATA (cont)FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)LEGENDRefer to this page for general Fan Performance notes.NOTES:1.Boldfac

Página 110 - PERFORMANCE DATA (cont)

88PERFORMANCE DATA (cont)ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 549B036-072LEGENDFIOP — Factory-Installed Option*The static pressure must be added

Página 111

89PERFORMANCE DATA (cont)OPTIONAL POWER EXHAUSTPOWER REQUIREMENTS INDOOR-FAN MOTOR DATA — 549B036-120LEGEND*Extensive motor and electrical testing on

Página 112

9OPTIONS AND ACCESSORIES (cont)This is included as a factory-installed option. It per-mits quick and simple indoor-fan access.This is included as a fa

Página 113

90PERFORMANCE DATA (cont)ELECTRIC HEATING CAPACITIES ELECTRIC HEATING CAPACITIES (cont)*Two heater packages required to provide kW indicated.†On units

Página 114 - ELECTRICAL DATA

91ELECTRICAL DATAUNITS WITHOUT ELECTRICAL CONVENIENCE OUTLETUNIT549BNOMINAL VOLTAGE(V-Ph-Hz)VOLTAGERANGECOMPRESSOR OFM IFMELECTRICHEAT*POWERSUPPLYMINI

Página 115 - TYPICAL WIRING SCHEMATIC

92ELECTRICAL DATA (cont)UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)LEGEND AND NOTES FOR ELECTRICAL DATA TABLES LEGEN

Página 116

93ELECTRICAL DATA (cont)UNITS WITH ELECTRICAL CONVENIENCE OUTLETUNIT549BNOMINAL VOLTAGE(V-Ph-Hz)VOLTAGERANGECOMPRESSOR OFM IFMELECTRICHEAT*POWERSUPPLY

Página 117 - 6T3 4T2 2T1 LOAD

94ELECTRICAL DATA (cont)UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)LEGEND AND NOTES FOR ELECTRICAL DATA TABLES LEGEND*U

Página 118

95TYPICAL WIRING SCHEMATIC549B036-12050TFQ004-012549B036-120

Página 119

96TYPICAL WIRING SCHEMATIC (cont)LEGEND FOR TYPICAL WIRING SCHEMATICIMPORTANT: Consult unit wiring label for actual wiring schematic.NOTES:1. If any o

Página 120

97GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITSPACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP — CONSTANT VOLUME APPLICATIONHVAC GUIDE SPECIFICATIONSSIZE RA

Página 121

98GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)b. E-Coated aluminum-fin coils shall have a flexibleepoxy polymer coating uniformly applied

Página 122

99GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)K. Electrical Requirements:All unit power wiring shall enter unit cabinet at a singlefactory