19
Number of Heat Stages – Indicates how many heat
stages are available for use. See configuration in
Appendix A for details on specific unit configuration.
Factory Default =1 for single heat stage units
2 for dual stage units
0 for cooling only units
Continuous Occupied Exhaust – This point tells the
controller when to run the power exhaust if equipped on
the unit.
If set to YES, the power exhaust will be on all the time
when in occupied mode and will be off when in
unoccupied mode. If set to NO the power exhaust will be
controlled by the Power Exhaust Setpoint.
Default = NO
RH Control -- Enables dehumidification control if an RH
sensor is available and the unit has the Perfect Humidity
t
dehumidification option installed.
Range =Disable/Enable
Default = Disable
(Enabled with Perfect Humidity option)
DCV Control -- Enables demand controlled ventilation
(DCV)ifvalidCO
2
sensor value is available and the unit
has an economizer installed.
Range = Disable/Enable
Default = Disable
System Space Temperature -- The network space
temperature value that the controller is using for control
(if applicable).
Range = N/A Default = --999.0_F
System Space RH -- The network relative humidity value
that the controller is using for control (if applicable)
Range = N/A Default = --999.0%
System Space AQ -- The network indoor air quality (CO
2
)
value that the controller is using for control (if applicable)
Range = N/A Default = --999.0 PPM
System Cool Demand Level -- The system cool demand
level being received over the network
Range = N/A Default = 0--3
System Heat Demand Level -- The system heat demand
level being received over the network
Range = N/A Default = --0--3
System Outdoor Air Temperature -- Allows the outdoor
air temperature value to be network readable when
enabled. Requires RTU Open to be equipped with an
outdoor air temperature sensor
Range = N/A Default = --999.0_F
System Outdoor AQ -- Allows network readable value of
OAQ for calculation during differential OAQ CO
2
levels
and IAQ CO
2
levels to drive the IAQ control
Range = N/A Default = --999.0 PPM
System Fire / Smoke -- Allows network readable fire/smoke
signal to invoke shutdown action in the RTU
Range = N/A Default = OFF
Indoor CO
2
Sensor Value @ Min mA – Sets the indoor
CO
2
value when the board reads 4 mA at input 1 or 2.
Range = 0 to 9999 ppm Default = 0 ppm
Indoor CO
2
Sensor Value @ Max mA – Sets the indoor
CO
2
value when the board reads 20 mA at input 1 or 2.
Range = 0 to 9999 ppm Default = 2000 ppm
Outdoor CO
2
Sensor Value @ Min mA – Sets the outdoor
CO
2
value when the board reads 4 mA at input 1 or 2.
Range = 0 to 9999 ppm Default = 0 ppm
Outdoor CO
2
Sensor Value @ Max mA – Sets the outdoor
CO
2
value when the board reads 20 mA at input 1 or 2.
Range = 0 to 9999 ppm Default = 2000 ppm
NOTE: The indoor and outdoor min and max mA setting
are used to set the linear curve of mA vs. PPM.
OPERATION
The RTU Open will control the compressors, economizer
and heating outputs based on its space temperature input
and setpoints. It can also be controlled by a building
control system or zoning system. An optional CO
2
IAQ
sensor mounted in the space can influence the economizer
minimum position. The RTU Open has a hardware clock
that can allow scheduling for stand-alone operation. The
RTU Open’s default is to control to occupied setpoints all
the time, until a type of occupancy control is set. The
following sections describe the operation for the functions
of the RTU Open.
Occupancy
Occupancy is the fundamental overall control of
equipment. The unit can be in one of two states: Occupied
or Unoccupied. These are usually referred to as periods
because they represent periods of any given day. Before
RTU Open can operate specific functions of the
equipment it is installed on, occupancy must be
determined. There are four different ways RTU Open can
determine occupancy. These are described below and
selected by the configuration point Occupancy Source.
Always Occupied (Default)
The unit will not determine occupancy and continuously
run in the occupied state or period. RTU Open ships from
the factory with this setting to allow immediate operation.
BACnet
R
Schedule
When Occupancy Source is set to BACnet Schedule, RTU
Open will use a schedule to change occupancy based upon
a day of week and a time period. Local time and date
should be set in the RTU Open for this function to operate
properly. This function applies if setting a local schedule
in the RTU Open or if applying the unit to a Building
Automation System or an Open zoning system. An Open
network schedule can override a local schedule within the
unit. A space sensor push button override is only available
when running a local or Open schedule. The push button
will override an unoccupied period to occupied for the
specified time duration.
BAS On/Off
When Occupancy Source is set to BAS On/Off, RTU
Open follows occupancy based on an On/Off command to
the BAS ON/OFF software point. An on command sets
the occupancy to occupied, and an off command sets it to
unoccupied. The Building Automation System can be
speaking BACnet, Modbus, N2, or LON and is writing to
the BAS On/Off point in the open protocol point map.
Remote Occ Input
When Occupancy Source is set to Remote Occ Input, RTU
Open follows occupancy based on the remote occupancy