CONFIGURATION POINTS (CON’T)
POINT NAME BACnet Object RANGE DEFAULT ENTRY
SERVICE CONFIGURATION
Unit Type unit_type 1=Heat/Cool
2=n/a
3=HP O/B Ctrl
4=HP Y1/W1 Ctrl
Heat/Cool (580/558J and 581/55J models)
HP Y1/W1 Ctrl (548J and 549J models)
Compressor Stages comp_stages 1=One Stage
2=Two Stages
One Stage (sizes 04-07, and A08-A12)
Two Stages (sizes 08-30)
Face Split Coil
4
face_split Yes/No No
Economizer Exists econ_exist No/Yes No (No FIOP)
Yes (FIOP)
Fan Control fan_type 1=Single Speed
2=Two Speed
3=Variable Speed
Single Speed (04-07 and A08-12)
Two Speed (units with VFD option)
VFD Input vfd_in_type 0-10Vdc/2-10Vdc 2-10Vdc
Max VFD Output max_vfd_spd 33-100% 100%
Min VFD Output min_vfd_spd 15-100% 40%
Dehum Min VFD Output dehum_min_vfd 50-100% 60%
Reversing Valve Output
5
rev_vlv_type O output type/B output type O output type
Heat Type heat_type Electric/Gas Gas (580J/581J Series Units)
Electric (558J/551J/548J/549j Series Units)
Number of Heat Stages heat_stages 1=1 stage
2=2 stages
3=0 stage
0 (558J/551J series cooling only units)
1 (All 548J and 549J, Low Nox units,
single phase gas units,
580/558J04-09 low and
580/558J05-07 med heat 3 phase gas units)
2 (580/558J04 and 08-09 med,
580/558J05-09 high heat 3 phase
gas units, 581/551J04-09 3 phase
gas units and All 12-30 gas units)
Continuous Occupied Exhaust occ_exh No/Yes No
RH Control rh_enable Disable/Enable Enable (Units with Perfect Humidity™)
Disable (Units w/o Perfect Humidity™)
DCV Control dcv_enable Disable/Enable Disable
Indoor CO2 Sensor Value @ Min mA iaq_ref_lo_ppm 0-9999ppm 0
Indoor CO2 Sensor Value @ Max mA iaq_ref_hi_ppm 0-9999ppm 2000
Outdoor CO2 Sensor Value @ Min mA oaq_ref_lo_ppm 0-9999ppm 0
Outdoor CO2 Sensor Value @ Max mA oaq_ref_hi_ppm 0-9999ppm 2000
System Space Temperature system_spt
System Space RH system_rh
System Space AQ system_iaq
System Outdoor AQ system_oaq
System Cool Demand Level cool_demand_level 0-3 0
System Heat Demand Level heat_demand_level 0-3 0
System Outdoor Air Temperature system_oat
SERVICE TEST
Service Test test_enable Disable/Enable Disable
Fan Test fan_test Disable/Enable Disable
High Speed Fan Test hi_spd_test Disable/Enable Disable
Compressor 1 Test comp1_test Disable/Enable Disable
Compressor 2 Test comp2_test Disable/Enable Disable
Heat 1 Test heat1_test Disable/Enable Disable
Heat 2 Test heat2_test Disable/Enable Disable
Reversing Valve Test rev_vlv_test Disable/Enable Disable
Dehumidification Test dehum_test Disable/Enable Disable
Power Exhaust Test pexh_test Disable/Enable Disable
Economizer Test econ_test 0-100 %Open 0
VFD Speed Test vfd_spd_test 0-100% 0
4
= This point is visible when Fan Control is configured f or Variable Speed
5
= This point is visible when Unit Type is configured for HP O/B Ctrl
TS---5580J---02