APPENDIX A -- USER INTERFACE MENUS (CON’T)
Field Assistant Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
SETPOINT
Properties>
Control Program>
Configuration>Setpoints
3 Occupied Heating Setpoint occupied_heat_setpoint 40-90 °F 70
3 Occupied Cooling Setpoint occupied_cool_setpoint 55-99 °F 76
3 Unoccupied Heating Setpoint unoccupied_heat_setpoint 40-90 °F 55
3 Unoccupied Cooling Setpoint unoccupied_cool_setpoint 45-99 °F 90
N/A Effective Heat Setpoint effective_heat_setpoint 0-120 °F
N/A Effective Cool Setpoint effective_cool_setpoint 0-120 °F
3 Optimal Start optm_start 0-4 hr 1
3 Optimal Start Type start_type 1=None
2=Temp Compensated
3=Learning Adaptive
Temperature Compensated
3 Heat Start K factor (min/deg) h_kfactor 0-99 15
3 Cool Start K factor (min/deg) c_kfactor 0-99 15
3 Occ Relative Humidity Setpoint occ_dehum_stpt 0-unocc setpoint %rh 60
3 Unocc Relative Humidity Setpoint unocc_dehum_stpt 30-100 %rh 95
3 DCV Max Ctrl Setpoint iaq_stpt_max 0-9999 ppm 650
3 Power Exhaust Setpoint
5
pexh_stpt 20-90 %Open 50
SPACE TEMPERATURE ALARM
Properties>
Control Program>
Configuration>
Alarm Configuration>
Space Temperature Alarm
3 Occupied Alarm Hysteresis occ_spt_alrm_hyst 0-20°F 5
N/A Alarm Delay (min/deg) spt_alrm_delay 0-60 minutes 10
3 Unoccupied Low SPT Alarm Limit uno_spt_alrm_lo_lmt 35-90 °F 45
3 Unoccupied High SPT Alarm Limit uno_spt_alrm_hi_lmt 45-100 °F 95
SUPPLY TEMPERATURE ALARM
Properties>
Control Program>
Configuration>
Alarm Configuration>
Supply Temperature Alarm
3 Low SAT Alarm Limit sat_lo_alrm_lim 15-90 °F 38
3 High SAT Alarm Limit sat_hi_alrm_lim 90-175 °F 160
SPACE HUMIDITY ALARM
Properties>
Control Program>
Configuration>
Alarm Configuration>
Space Humidity Alarm
3 Occupied High RH Alarm Limit (%RH) sprh_hi_alrm_lim 0-100%rh 70%rh
3 Alarm Delay (min/%RH) sprh_delay 0-30 min 5min
3 Unoccupied High RH Alarm Limit (%RH) unocc_sprh_lmt 0-100%rh 100%rh
N/A Low RH Alarm Limit (%RH) sprh_lo_alrm_lim 0-100%rh 30%rh
IAQ / VENTILATION ALARM
Properties>
Control Program>
Configuration>
Alarm Configuration>
IAQ /Ventilation Alarm
3 Occupied High CO2 Alarm Limit (ppm) iaq_occ_hi_lmt 0-9999 ppm 1200
5
= This point is hidden from view when Continuous Occupied Exhaust is enabled