Five-- Minute Compressor Timeguard
This timer prevents the compressor from starting unless it has been of f for 5
minutes. It can be defeated for one cycle by simultaneously pressing the FAN
and UP keys.
Minimum On Timer
Once the equipment has been turned on, it must remain on for 3 minutes. A
change in mode or setpoint will cancel this timer.
Cycle Timer
Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or
10 minutes. This much time must elapse from the start of one cycle before
another cycle can start. It serves to impose the cycles per hour limits. It can be
defeated for one cycle by simultaneously pressing the FAN and UP keys.
Auto Changeover Timer
To prevent unnecessary cycling between heating and cooling modes, this timer
prevents a changeover to the opposite mode until a demand exists in the opposite
mode for 20 minutes. It is defeated when setpoints are changed so that the
opposite mode is immediately available if desired.
Error Codes
Two error messages indicate problems with the thermostats operation. If the
room temperature sensor fails, the temperature display will show ----, two dashes.
If there is an internal memory failure, the temperature display will show E4. The
remedy for each of these is to replace the thermostat.
Table 1 shows the thermostat outputs for each available stage of heating or
cooling. It may be useful in checkout or troubleshooting.