Figure 19. Low Voltage Field Wiring
Thermostat Connections
The thermostat should be wired directly to the ICM2
control board as shown in Figure 19. Consult the
Thermostat section for speci c wiring.
Water Freeze Protection - FP1
The CXM/DXM control allows the eld selection of
source uid freeze protection points. The factory setting
of FP1 is set for water (30°F). In earth loop applications
jumper JW3 (FP1- antifreeze 10°F) should be clipped as
shown in Figure 20 to change the setting to 10°F, a more
suitable temperature when using antifreezes in colder
earth loops.
Air Coil Freeze Protection - FP2
The Air coil freeze protection is factory set at 30°F and
should not need adjusting.
Figure 20. Changing FP1-Freeze Protection Setpoint
CXM PCB
Clip this JW3-
FP1 jumper
for anti-freeze
systems
Electrical - Low Voltage
Transformer
Compressor A
Contactor
L1
L2
208-230/60/1
4 Amp Max.
Source Pump
Ground
PR
ICM2
Controller
Pump
Circt Brkr
with ground
(see Elect. Table for wire
and Brkr. size)
Compressor B
Contactor
CXM Control - A
Low Voltage
Connector
CXM Control - B
Low Voltage
Connector
HWG
Install HWG Pump
Power after insuring
water is in HWG circuit
Yellow
Blk
External Loop Pump(s)
Table 6. Blower performance table and fan speed selection
Max Fan
Normal Mode Dehumid Mode
Aux Aux
Model ESP Motor
Tap
Htg & Normal Clg CFM Emerg
(in wg) (hp)
Setting
Stg 2 Stg 1 Fan Stg 2 Stg 1 Fan
Setting Mode
4 1290 710 650 1010 550 650 4 1290
036 0.5 1/2 3 1200 660 600 940 520 600 3 1200
2 1110 610 560 870 480 560 2 1110
1 1020 560 510 1 1020
4 1450 800 730 1130 620 730 4 1450
042 0.5 1/2 3 1400 770 700 1090 600 700 3 1400
2 1300 720 650 1010 560 650 2 1300
1 1190 660 600 1 1190
4 1720 950 860 1340 740 860 4 1720
048 0.75 1 3 1600 880 800 1250 690 800 3 1600
2 1480 810 740 1150 630 740 2 1480
1 1360 750 680 1 1360
4 2150 1180 1080 1680 920 1080 4 2150
060 0.75 1
3 2000 1100 1000 1560 860 1000 3 2000
2 1850 1020 930 1440 800 930 2 1850
1 1700 940 850 1 1700
4 2250 1280 1130 1760 1000 1130 4 2250
072 0.75 1 3 2130 1210 1070 1660 940 1070 3 2130
2 2000 1140 1000 1560 890 1000 2 2000
1 1900 1080 950 1 1900
Rev.: 07/06/05D
Bold figures indicate factory settings, setting on all models.
These values represent Left return models. For right return units move the CFM adj from (norm) to the (+) setting.
During Auxiliary operation the CFM will run at the higher of the HP or AUX settings.
Airflow is controlled within ± 5% up to Max ESP shown with wet coil and with 1" throwaway filter.
Standard 1" electrostatic filter will add 0.15 in wg when clean.
When Dehumidification mode is selected, HP CFM setting must be 4, 3, or 2 only.
All units ARI/ISO/ASHRAE 13256-1 rated at maximum external static.
ECM FAN MOTOR