Accessory Connections
A terminal paralleling the compressor contactor coil have
been provided on the CXM/DXM control of the GT-X
line. "A" has been provided to control accessory devices,
such as water valves, electronic air cleaners, humidi ers,
etc. Note: This terminal should be used only with 24
volt signals and not line voltage signals. This signal
operates with the compressor contactor. See Figure 21 or
the wiring schematic for details.
Figure 21. Accessory Wiring
Terminal Strip
Typical
Water
Valve
C
A
24VAC
Figure 22. Well Water AVM Valve Wiring
Water Solenoid Valves
When using solenoid valves on ground water installations.
Figure 21 illustrates a typical well water control valve
wiring which will limit wasted water during a lockout
condition. A slow closing valve may be required to
prevent water hammer. When using an AVM -Taco Slow
Closing valves on GT-X Series equipment Figure 22
wiring should be utilized. The valve takes approximately
60 seconds to open (very little water will ow before 45
seconds) and it activates the compressor only after the
valve is completely opened (by closing its end switch).
Only relay or triac based electronic thermostats should
be used with the AVM valve. When wired as shown, the
valve will operate properly with the following notations:
1 - The valve will remain open during a unit lockout.
2 - The valve will draw approximately 25-35 VA through
the “Y” signal of the thermostat. Note: This can
overheat the anticipators of electromechanical
thermostats. Therefore only relay or triac based
thermostats should be used.
C
GT-X
C
Thermostat
Y
1
2
3
Y
AVM
Taco Valve
Heater Switch
Thermostat Selection and Wiring
Figure 23a: Thermidistat
(Carrier TSTATCCPRH01)
(Bryant TSTATBBPRH01)
Figure 23b: Non-Programmable Thermostat
(Carrier TSTATCCN2S01)
(Bryant TSTATBBN2S01)
Note:
1. Thermostat DIP switches must be con gured for heat pump.
2.
Thermostat control con guration options must be set-up to activate "G"
call when there is a "W" call in order for electric heat to operate correctly.
3. Thermostat should be con gured for two-stage operation for units with
ECM fan motor to take advantage of the ECM features.
Rev.: 12/29/04D
ECM2 Board
TSTAT CCPRH01
or BBPRH01
Y/Y2
Y1/W2
W/W1
O/W2
G
R
DHum
C
Hum
B
S1
S2
Outdoor
Sensor
Humidifier
Solenoid
Valve
(24VAC)
Y2
Y1
W1
A
O
G
R
DH
or
Hum
C
L
Rev.: 07/18/05D
ECM2 Board
TSTAT CCN2S01
or BBN2S01
Y/Y2
Y1
W/W1
O
G
R
C
Y2
Y1
W1
A
O
G
R
C
L