Page 21
Diagnostic Features
The Status LED on the CXM control advises the
serviceman of the current status of the CXM control. The
status LED can display either the current CXM mode or
the last fault memory if in test mode. See Table 7 for a
complete listing of codes.
Unit Operation Description
PowerUp - The unit will not operate until all the inputs
and safety controls are checked for normal conditions.
Note: The compressor will have a 5 minute anti-short
cycle delay at power-up.
Standby - In Standby mode, Y and W inputs are not
active. Inputs O and G may be active. Compressor will
be off.
Cooling - To enter Cooling mode, Y and O become active. The
fi rst time after power-up that there is a call for compressor,
the compressor will follow a 5 to 80 second random start
delay. There will also be a 5 min compressor anti-short cycle
protection time as well. After the random start delay, the
compressor relay is energized. On all subsequent compressor
calls, the random start delay is omitted.
Heating Stage 1 - To enter Heating Stage 1 mode, Y
becomes active. The fi rst time after power-up that there
is a call for compressor, the compressor will follow a 5 to
80 second random start delay. There will also be a 5 min
compressor anti-short cycle protection time as well. After
the random start delay, the compressor relay is energized.
On all subsequent compressor calls, the random start
delay is omitted.
Heating Stage 2 - To enter Heating Stage 2 mode, W
becomes active (Y already active). The Compressor
relay remains on. EH1 is turned on immediately. With
continuing Heating Stage 2 demand, EH2 will turn on
after 10 minutes. The EH2 will not turn on in heating (or
will turn off if already on) if loop temperature is above
approximately 50°F (FP1 >45°F).
Emergency Heat - In Emergency Heat mode, W
becomes active while Y is not active. EH1 is turned on
immediately. With continuing Emergency Heat demand,
EH2 will turn on after 5 minutes. The FP1 and FP2
temperatures do not effect emergency heat operation.
Table 8. Fault Description Table
ICM2 Control Board
The GT-X also employs an ICM2 board that features:
• Thermostat terminal connections
• Thermostat signal diagnostic LED's
• Airfl ow selection
• Airfl ow LED (100 cfm per fl ash)
• Dehumidifi cation Mode Jumper
Fault
Fault LED
Code
Fault Condition
High Pressure Switch 2 HP Open Instantly
Low Pressure Switch or LOC 3
LP open for 30 continuous seconds before or
during a call (bypassed for first 60 seconds)
Freeze Protection Coax - FP1 4
FP1 below Temp limit for 30 continous seconds
(bypassed for first 60 seconds of operation)
Freeze Protection Air Coil - FP2 5
FP2 below Temp limit for 30 continous seconds
(bypassed for first 60 seconds of operation)
Condensate overflow 6
Sense overflow (grounded) for 30 continous
seconds
Over/Under Voltage Shutdown 7 (Autoreset) "R" power supply is <19VAC or >30VAC